Plan Review Notes
Plan Review Notes For Permit 06031370
Permit Number 06031370
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-07 00:00:00******** UNSAT ************
  
 1) NOTE: PLEASE SEE MECHANICALNOTES AS
 COPIES OF SIGNED, DATED AND SEALED PLANS
 WERE MADE OF THE ELECTRICAL PLANS AND
 MECHANICAL LAYOUT ADDED TO ARCHITECTS
 PLANS WHICH IS NOT PERMITTED.
 ** PLEASE SEE COMMENTS BELOW PERTAINING
 TO CORRELATE OF MECH AND ELEC PLANS.
  
 2) NOTE: PLEASE SEE BLDG REVIEW NOTES,
 AS TRUSS LAYOUT/ENGINEERING, CONTAINS A
 "RUBBER STAMP" FOR THE REQUIRED ORIGINAL
 SIGNATURE FORTHE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025
  
 3) NOTE: PLEASE SEE RISER INDICATES
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 THE METER TO THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 250.6,250.24B.
  
 4) NOTE: PLEASE SEE MIN SIZE FOR
 GROUNDING ELECTRODE SYSTEM SHALL BE
 SIZED ACCORD TO 250.66. SHOWS #4 WHICH
 IS MOST UNLIKELY FOR A 600A SERVICE AS
 SHOWN.
  
 5) NOTE: PLEASE SEE SEC'S FROM FPL ARE
 SHOWN AS ONE RUN OF COPPER CONDUCTORS
 SIZED AT 4/0'S. PLEASE KNOW, THIS ARE
 NOT LARGE ENOUGH FOR A 600A SERVICE.
 PLEASE SEE 310.16, 240.4 FOR SIZING MIN
 SEC'S TO FPL HANDHOLE.
  
 6) NOTE: PLEASE CORRLELATE ALL A/C
 EQUIPMENT FOR CU'S AND AHU'S.
 PLEASE SEE PLANS INDICATE 5 CU'S, YET
 PANELS, LOADS AND MECH PLANS DO NOT
 CORRELATE WITH THIS.
 215.5
  
 7) NOTE: PLEASE SEE MIN OCP FOR AHU'S
 HEAT SHALL BE SIZED PER 424.3B EVEN IF
 EXISTING. MIN OCP IS TO BE SIZED @ 125%.
  
 8) NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
 PLEASE CORRELATE ALL LOADS ON PANEL
 SCHEDULES WITH LOAD CALCS. (SMALL APPL
 ETC).
 PLEASE PROVIDE PANEL SCHEDULES AND LOAD
 CALCS FOR OTHER PANELS NOT SUBMITTED.
 PLEASE BE SURE ADJUST LOAD CALCS.
 215.5
  
 9) NOTE: PLEASE VERIFY POOL PUMP BEING
 SHOWN ON SCHEDULE "A" WHEN PLANS
 INDICATE A POOL PANEL.
 THIS IS ONLY A NOTE:
  
 10) NOTE: PLEASE SEE PLANS MISSING
 EITHER NEW OR EXISTING FRONT GFI PER
 210.52E,210.8A
  
 11) NOTE: PLEASE SEE SOME MISSING
 RECEPTS PER 210.52 REDLINED ON ONE OF
 THE SETS OF PLANS. BEDRM #4(2' OF WALL),
 LIVING/KITCHEN WALL.
 PLEASE SEE DUE TO THE LEVEL OF
 ALTERATION THE RECEPT ON LOWER LEVEL
 ADJACENT TO KITCHEN REMODEL WILL BE
 REQUIRED IF ONE IS NOT EXISTING.
  
 12) NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING GFI RECEPTS ALONG KITCHEN
 COUNTER SPACE.
  
 13) NOTE: PLEASE SEE 250.50 WHICH
 REQUIRES ANY NEW FOOTINGS TO BE BONDED
 TO THE EXISITNG GROUNDING ELECTRODE
 SYSTEM.
 PLEASE REVISE AND INDICATE THIS ON
 RISER.
  
 14) NOTE: PLEASE INDICATE THE REQUIRED
 ARC FAULT PROTECTION FOR ALL PER 2002
 NEC 210.12B.
 SD'S, LTS, RECEPTS, FANS ETC IN SLEEPING
 RMS.
  
 15) NOTE: PLEASE SEE 210.52D AS THE GFI
 RECEPTS IN BATHS LOCATED ADJACENT TO
 LAV'S SHALL BE LOCATED WITHIN 3' FROM
 LAV EDGE.
 (PLEASE SEE HIS BATH) MASTER)
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** WHEN RE-SUBMITTING PLANS, PLEASE
 COMPLETELY REMOVED ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF ANY OLD/VOIDED
 REMOVED SHEETS SHOULD BE BE SUBMITTED
 FOR REFERENCE AS AN INDIVIDUAL SET.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]