| 2006-04-07 00:00:00 | ******** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE MECHANICALNOTES AS |
| | COPIES OF SIGNED, DATED AND SEALED PLANS |
| | WERE MADE OF THE ELECTRICAL PLANS AND |
| | MECHANICAL LAYOUT ADDED TO ARCHITECTS |
| | PLANS WHICH IS NOT PERMITTED. |
| | ** PLEASE SEE COMMENTS BELOW PERTAINING |
| | TO CORRELATE OF MECH AND ELEC PLANS. |
| | |
| | 2) NOTE: PLEASE SEE BLDG REVIEW NOTES, |
| | AS TRUSS LAYOUT/ENGINEERING, CONTAINS A |
| | "RUBBER STAMP" FOR THE REQUIRED ORIGINAL |
| | SIGNATURE FORTHE ENGINEER OF RECORD. |
| | PLEASE SEE FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE RISER INDICATES |
| | "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| | THE METER TO THE FIRST MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. |
| | 250.6,250.24B. |
| | |
| | 4) NOTE: PLEASE SEE MIN SIZE FOR |
| | GROUNDING ELECTRODE SYSTEM SHALL BE |
| | SIZED ACCORD TO 250.66. SHOWS #4 WHICH |
| | IS MOST UNLIKELY FOR A 600A SERVICE AS |
| | SHOWN. |
| | |
| | 5) NOTE: PLEASE SEE SEC'S FROM FPL ARE |
| | SHOWN AS ONE RUN OF COPPER CONDUCTORS |
| | SIZED AT 4/0'S. PLEASE KNOW, THIS ARE |
| | NOT LARGE ENOUGH FOR A 600A SERVICE. |
| | PLEASE SEE 310.16, 240.4 FOR SIZING MIN |
| | SEC'S TO FPL HANDHOLE. |
| | |
| | 6) NOTE: PLEASE CORRLELATE ALL A/C |
| | EQUIPMENT FOR CU'S AND AHU'S. |
| | PLEASE SEE PLANS INDICATE 5 CU'S, YET |
| | PANELS, LOADS AND MECH PLANS DO NOT |
| | CORRELATE WITH THIS. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE MIN OCP FOR AHU'S |
| | HEAT SHALL BE SIZED PER 424.3B EVEN IF |
| | EXISTING. MIN OCP IS TO BE SIZED @ 125%. |
| | |
| | 8) NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS. |
| | PLEASE CORRELATE ALL LOADS ON PANEL |
| | SCHEDULES WITH LOAD CALCS. (SMALL APPL |
| | ETC). |
| | PLEASE PROVIDE PANEL SCHEDULES AND LOAD |
| | CALCS FOR OTHER PANELS NOT SUBMITTED. |
| | PLEASE BE SURE ADJUST LOAD CALCS. |
| | 215.5 |
| | |
| | 9) NOTE: PLEASE VERIFY POOL PUMP BEING |
| | SHOWN ON SCHEDULE "A" WHEN PLANS |
| | INDICATE A POOL PANEL. |
| | THIS IS ONLY A NOTE: |
| | |
| | 10) NOTE: PLEASE SEE PLANS MISSING |
| | EITHER NEW OR EXISTING FRONT GFI PER |
| | 210.52E,210.8A |
| | |
| | 11) NOTE: PLEASE SEE SOME MISSING |
| | RECEPTS PER 210.52 REDLINED ON ONE OF |
| | THE SETS OF PLANS. BEDRM #4(2' OF WALL), |
| | LIVING/KITCHEN WALL. |
| | PLEASE SEE DUE TO THE LEVEL OF |
| | ALTERATION THE RECEPT ON LOWER LEVEL |
| | ADJACENT TO KITCHEN REMODEL WILL BE |
| | REQUIRED IF ONE IS NOT EXISTING. |
| | |
| | 12) NOTE: PLEASE SEE 210.52C1 FOR SOME |
| | MISSING GFI RECEPTS ALONG KITCHEN |
| | COUNTER SPACE. |
| | |
| | 13) NOTE: PLEASE SEE 250.50 WHICH |
| | REQUIRES ANY NEW FOOTINGS TO BE BONDED |
| | TO THE EXISITNG GROUNDING ELECTRODE |
| | SYSTEM. |
| | PLEASE REVISE AND INDICATE THIS ON |
| | RISER. |
| | |
| | 14) NOTE: PLEASE INDICATE THE REQUIRED |
| | ARC FAULT PROTECTION FOR ALL PER 2002 |
| | NEC 210.12B. |
| | SD'S, LTS, RECEPTS, FANS ETC IN SLEEPING |
| | RMS. |
| | |
| | 15) NOTE: PLEASE SEE 210.52D AS THE GFI |
| | RECEPTS IN BATHS LOCATED ADJACENT TO |
| | LAV'S SHALL BE LOCATED WITHIN 3' FROM |
| | LAV EDGE. |
| | (PLEASE SEE HIS BATH) MASTER) |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** WHEN RE-SUBMITTING PLANS, PLEASE |
| | COMPLETELY REMOVED ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE COPY OF ANY OLD/VOIDED |
| | REMOVED SHEETS SHOULD BE BE SUBMITTED |
| | FOR REFERENCE AS AN INDIVIDUAL SET. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |