| Plan Review Notes For Permit 06031370 |
| Permit Number |
06031370 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-01 00:00:00 | | | | | | | DENIED | | | | | | 1) WIND DESIGN CRITERIA ON TITLE PAGE | | | INCORRECT, SHOULD BE ASCE 7-02 | | | | | | 2) SUBMIT ENGINEERED TRUSS DRAWINGS THAT | | | COMPLY WITH R802.10.1 FBC WITH PERMIT | | | APPLICATION OR BEFORE INSTALLATION | | | | | | 3) STAIRS ON A2 SHOW 10 RISERS AT 7" TO | | | LANDING. DRAWING STATES LANDING AT 5'-4 | | | 3/16" PLEASE CLARIFY | | | | | | 4) INDICATE MINIMUM ROOF SHEATHING NAIL | | | PATTERN AS SPECIFIED IN TABLE 2304.9.1 | | | | | | 5) WHEN POSSIBLE FLORIDA PRODUCT | | | APPROVAL COVER SHEETS SHALL BE SUBMITTED | | | THE ONLY PRODUCT THAT REQUIRES IT IS THE | | | ROOF TILES. PLEASE SEE FL# 282-R1 | | | | | | 6) PRODUCT APPROVAL FOR CASEMENT WINDOWS | | | HAVE A MAXIMUM HEIGHT OF 72", THE NEW | | | DINING ROOM WINDOW EXCEEDS THE MAX. HT. | | | | | | 7) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | |
|