Plan Review Notes For Permit 06031357
Permit Number 06031357
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-17 00:00:00*** UNSAT ***
  
 ** PLANS ARE TEMPORARILY FAILED FOR
 ELECTRICAL REVIEW.
  
 1) NOTE: PLEASE TWO DIFFERENT SETS OF
 FLORIDA ENERGY CALCULATIONS WERE
 SUBMITTED. PLEASE SEE EACH SHOW
 DIFFERENT SQ FT?
 PLEASE SEE EACH, ONLY ONE SIGNED, DATED
 AND SEALED BY THE ENGINEER FOR DESIGNS.
 PLEASE SEE CONTROLS FOR LIGHTING ARE
 LISTED AS MANUAL /ON/OFF??
  
 PLEASE SEE AT THIS TIME THE LIGHTING
 POWER USEAGE APPEARS IT MAY BE OK, BUT
 IT IS UNCLEAR AT THIS TIME.
  
 2) NOTE: PLEASE SUBMIT MANUFACTURE'S
 SPEC/CUT SHEETS FOR THE NEW PROPOSED
 LIGHTING CONTROL SYSTEM(S). PLEASE
 SUBMIT A LAYOUT FOR EACH SYSTEM ,AND
 ZONE, FOR FLR AND EACH LEVEL.
  
 ELECTRICAL PLANS ARE OK, AS LONG AS
 FIXTURES REMAINS THE SAME.
  
 **PLEASE AHVE ENGINEER OF RECORD CALL TO
 GO OVER THESE COMMENTS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER2WPB.ORG