| Plan Review Notes For Permit 06031357 |
| Permit Number |
06031357 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-09-17 00:00:00 | *** UNSAT *** | | | | | | ** PLANS ARE TEMPORARILY FAILED FOR | | | ELECTRICAL REVIEW. | | | | | | 1) NOTE: PLEASE TWO DIFFERENT SETS OF | | | FLORIDA ENERGY CALCULATIONS WERE | | | SUBMITTED. PLEASE SEE EACH SHOW | | | DIFFERENT SQ FT? | | | PLEASE SEE EACH, ONLY ONE SIGNED, DATED | | | AND SEALED BY THE ENGINEER FOR DESIGNS. | | | PLEASE SEE CONTROLS FOR LIGHTING ARE | | | LISTED AS MANUAL /ON/OFF?? | | | | | | PLEASE SEE AT THIS TIME THE LIGHTING | | | POWER USEAGE APPEARS IT MAY BE OK, BUT | | | IT IS UNCLEAR AT THIS TIME. | | | | | | 2) NOTE: PLEASE SUBMIT MANUFACTURE'S | | | SPEC/CUT SHEETS FOR THE NEW PROPOSED | | | LIGHTING CONTROL SYSTEM(S). PLEASE | | | SUBMIT A LAYOUT FOR EACH SYSTEM ,AND | | | ZONE, FOR FLR AND EACH LEVEL. | | | | | | ELECTRICAL PLANS ARE OK, AS LONG AS | | | FIXTURES REMAINS THE SAME. | | | | | | **PLEASE AHVE ENGINEER OF RECORD CALL TO | | | GO OVER THESE COMMENTS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | DPALMER2WPB.ORG |
|