Plan Review Notes
Plan Review Notes For Permit 06031357
Permit Number 06031357
Review Stop P
Sequence Number 2
Notes
Date Text
2006-08-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW:
  
 1. SURVEY SHEET 1 OF 1 PER FS 472.025
 ALL FINAL DRAWINGS, PLANS ETC. PREPARED
 BY THE REGISTRANT SHALL BE SIGNED,
 SEALED, AND DATED BY THE RESISTRANT.
 ****RESPONSE NOTED, BUT SURVEY SUBMITTED
 HAS NOT CHANGED AND IS NOT SIGNED,
 SEALED, AND DATED.
  
 2. OK
  
 3. SHT A2.1 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS AS
 REQUIRED IN SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS. SHOW THE SF OF EACH
 AREA BEING DRAINED, ALONG WITH 1/2 THE
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND SHOW THE AREAS OF ROOFS
 THAT DRAIN ONTO THE ROOF AREAS FROM
 ABOVE IN CLACULATIONS. - IT APPEARS THAT
 NEW AREA WILL BE ADDED TO THE ROOF AREAS
 IN THE FORM OF NEW ROOF/WALL AREAS AT
 ENTRANCES.
 ****RESPONSE NOTED, BUT CALCULATIONS
 WERE NOT FOUND, AND LOCATION OF
 CALCULATIONS NOT INDICATED IN RESPONSE.
  
 4. SHT A2.1 THE NEW OVERFLOW SCUPPERS
 SIZING CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE INDICATE THAT SCUPPERS WERE SIZED
 TO COMPLY WITH SECTIONS 1101.7, 1107.3 &
 TABLE 1106.7.
 ****RESPONSE NOTED, BUT HEIGHT AND WIDTH
 OF OVERFLOW SCUPPERS ARE REQUIRED TO
 DETERMINE THE AREA OF THE SCUPPER.
  
 5. SHT A6-1 THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE WITH
 ACCESSIBILITY:
 FOR DRINKING FOUNTAINS:
 A. 11-4.15.5 CLEAR FLOOR SPACE
 ****NOT ADDRESSED, NO RESPONSE
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NOT ADDRESSED, NO RESPONSE
 B. 11-4.16.6 DISPENSERS
 ****NOT ADDRESSED, NO RESPONSE
 FOR TOILET STALLS:
 A. 11-4.17.3 (EXCEPTION) LAV SHALL BE
 LOCATED 60" OFF W/C WALL TO SIDE OF THE
 FIXTURE PER FIGURE 30E. IT SCALES OUT TO
 BE APPROXIMATELY 58".
 ****NOT ADDRESSED, NO RESPONSE
 FOR URINALS:
 A. 11-4.18.2 HEIGHT
 ****NOT ADDRESSED, NO RESPONSE
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED, NO RESPONSE
 C. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED, NO RESPONSE
 FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****NO RESPONSE, BUT CLEAR FLOOR SPACE
 IS NOT INDICATED IN TOILET ROOMS 162,
 163.
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****NOT ADDRESSED, NO RESPONSE
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED, NO RESPONSE
 FOR THE TOILET ROOMS:
 A. 11-4.22.3 UNOBSTRUCTED TURNING IN
 TOILET ROOM. (NOT IN STALLS).
 ****NO RESPONSE, NOT ADDRESSED. SEE
 TOILET ROOMS 129, & 131.
  
 6. SHT A9.4 DETAILS 03, 04, 05, & 06
 SHOW THE FOLLOWING TO SHOW COMPLIANCE:
  
 A. OK
 B. OK
  
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 ****NOT ADDRESSED, NO RESPONSE
  
 7. OK
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]