| Date |
Text |
| 2006-08-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. FROM PREVIOUS REVIEW: |
| | |
| | 1. SURVEY SHEET 1 OF 1 PER FS 472.025 |
| | ALL FINAL DRAWINGS, PLANS ETC. PREPARED |
| | BY THE REGISTRANT SHALL BE SIGNED, |
| | SEALED, AND DATED BY THE RESISTRANT. |
| | ****RESPONSE NOTED, BUT SURVEY SUBMITTED |
| | HAS NOT CHANGED AND IS NOT SIGNED, |
| | SEALED, AND DATED. |
| | |
| | 2. OK |
| | |
| | 3. SHT A2.1 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS AS |
| | REQUIRED IN SECTIONS 1106 & 1107 WITH |
| | ALL SUBSECTIONS. SHOW THE SF OF EACH |
| | AREA BEING DRAINED, ALONG WITH 1/2 THE |
| | AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS, AND SHOW THE AREAS OF ROOFS |
| | THAT DRAIN ONTO THE ROOF AREAS FROM |
| | ABOVE IN CLACULATIONS. - IT APPEARS THAT |
| | NEW AREA WILL BE ADDED TO THE ROOF AREAS |
| | IN THE FORM OF NEW ROOF/WALL AREAS AT |
| | ENTRANCES. |
| | ****RESPONSE NOTED, BUT CALCULATIONS |
| | WERE NOT FOUND, AND LOCATION OF |
| | CALCULATIONS NOT INDICATED IN RESPONSE. |
| | |
| | 4. SHT A2.1 THE NEW OVERFLOW SCUPPERS |
| | SIZING CAN NOT BE DETERMINED WITHOUT |
| | REFERENCE TO THE DEFLECTION OF THE ROOF. |
| | PLEASE INDICATE THAT SCUPPERS WERE SIZED |
| | TO COMPLY WITH SECTIONS 1101.7, 1107.3 & |
| | TABLE 1106.7. |
| | ****RESPONSE NOTED, BUT HEIGHT AND WIDTH |
| | OF OVERFLOW SCUPPERS ARE REQUIRED TO |
| | DETERMINE THE AREA OF THE SCUPPER. |
| | |
| | 5. SHT A6-1 THE FOLLOWING INFORMATION IS |
| | REQUIRED TO SHOW COMPLIANCE WITH |
| | ACCESSIBILITY: |
| | FOR DRINKING FOUNTAINS: |
| | A. 11-4.15.5 CLEAR FLOOR SPACE |
| | ****NOT ADDRESSED, NO RESPONSE |
| | FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ****NOT ADDRESSED, NO RESPONSE |
| | B. 11-4.16.6 DISPENSERS |
| | ****NOT ADDRESSED, NO RESPONSE |
| | FOR TOILET STALLS: |
| | A. 11-4.17.3 (EXCEPTION) LAV SHALL BE |
| | LOCATED 60" OFF W/C WALL TO SIDE OF THE |
| | FIXTURE PER FIGURE 30E. IT SCALES OUT TO |
| | BE APPROXIMATELY 58". |
| | ****NOT ADDRESSED, NO RESPONSE |
| | FOR URINALS: |
| | A. 11-4.18.2 HEIGHT |
| | ****NOT ADDRESSED, NO RESPONSE |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | ****NOT ADDRESSED, NO RESPONSE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ****NOT ADDRESSED, NO RESPONSE |
| | FOR LAVS: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | ****NO RESPONSE, BUT CLEAR FLOOR SPACE |
| | IS NOT INDICATED IN TOILET ROOMS 162, |
| | 163. |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | ****NOT ADDRESSED, NO RESPONSE |
| | C. 11-4.19.5 FAUCETS |
| | ****NOT ADDRESSED, NO RESPONSE |
| | FOR THE TOILET ROOMS: |
| | A. 11-4.22.3 UNOBSTRUCTED TURNING IN |
| | TOILET ROOM. (NOT IN STALLS). |
| | ****NO RESPONSE, NOT ADDRESSED. SEE |
| | TOILET ROOMS 129, & 131. |
| | |
| | 6. SHT A9.4 DETAILS 03, 04, 05, & 06 |
| | SHOW THE FOLLOWING TO SHOW COMPLIANCE: |
| | |
| | A. OK |
| | B. OK |
| | |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | ****NOT ADDRESSED, NO RESPONSE |
| | |
| | 7. OK |
| | 8. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |