| Date |
Text |
| 2006-07-16 00:00:00 | ********* UNSAT2ND REVIEW ********* |
| | |
| | ** PLEASE SEE COMMENTS BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE RESPONSE |
| | MENTIONS THIS IS COMPLIED WITH, HOWEVER |
| | PLANS DO NOT INDICATE ANY SYSTEM FOR THE |
| | FIRST FLOOR OR 2NF FLR AS EACH FLR SHALL |
| | BE SEAPARATE. PLEASE SEE MOST ROOMS |
| | WHICH ARE CONSIDERED "SEPARATE SPCES" |
| | WITH FLOOR TO CEILING HEIGHT PARTITIONS |
| | ALSO REQUIRE SEPARATE CONTROLS WHICH |
| | WOULD OVER RIDE ANY TIME OF DAY |
| | SCHEDULEING ETC. PLEASE ALSO SEE OVER |
| | RIDE DEVICE LOCATIONS ARE REQUIRED TO BE |
| | SHOWN ON PLANS AT LOCATIONS AT THE PINT |
| | OF ENTRANCE(S) TO SPACE(S)AND HAVE |
| | VISABILITY OF LIGHTING IN WHICH THE OVER |
| | RIDE DEVICE CONTROLS. |
| | COULD NOT LOCATE THE VOLTAGE DROP WORST |
| | CASE FOR LONGER RUNS, (SITE LIGHTING)? |
| | PLEASE CLARIFY THE LIGHTING POWER |
| | DENSITIES (LPD). THE ENERGY CALCS SEEM |
| | TO INDICATE LIGHTING POWER DESIGN AT |
| | 18,688 AND 23,760 ALLOWED, PLEASE |
| | CLARIFY THE LPD USED. PLEASE ALSO SEE |
| | CONTROLS MENTIONS MANUAL ON/OFF?? |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2,.1.3, |
| | 13-415.1.AB.1,13-415.1.ABC.1 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS ARE COMING IN |
| | UNDER THE 2004 FBC. PLEASE SEE CHAPTER |
| | 13, 13-413.1ABC.1. FOR VOLTAGE DROP |
| | CALCS TO BE PROVIDED FOR WORST CASE |
| | SCENERIO. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, |
| | PLEASE PROVIDE ALL INFORMATION FOR |
| | LIGHTING CONTROL SYSTEM, TIME OF DAY, |
| | TYOE OF DEVICES, SYSTEMS ETC. |
| | INDICATE THE SECTION(S) AND PLEASE SEE |
| | MULTIPLE FLOOR REQUIREMENTS FOR |
| | ADDTIONAL CONTROLS. |
| | PLEASE SEE 13-413.1.ABC.2.2 |
| | PLESASE SEE 13-415.1.ABC.3 |
| | |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO, PLEASE SEE THIS WAS ONLY |
| | CHANGED ON "A" SHEETS. PLEAS KNOW, DUE |
| | TO REVISIONS ON ELECTRICAL SHEETSWHICH |
| | SOME WERE REVISED AND SOME WERE NOT, |
| | PLEASE BE SURE TO CHANGE THE DOOR SWING. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MAIN ELECTRICAL ROOM |
| | DOOR SHALL OPEN OUTWARD AND BE EQUIPPED |
| | WITH PANIC HARDWARE. |
| | 110.26 |
| | |
| | 4) NOTE: OK, REVISED FIX TYPE. |
| | |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: NO/YES, PLEASE SEE RISER STILL |
| | ONLY MENTIONS IN NOTES THAT THE |
| | GROUNDING ELECTRODE SYSTEM PER NEC AND |
| | NOTE FOR TRANSFORMER ALSO MENTIONS PER |
| | NEC. PLEASE SEE THESE NOTES SHOULD |
| | REFERENCE THE DETAILS ON 7-1. PLEASE |
| | REVISE NOTES. |
| | PLEASE ALSO KNOW, EXISTING FOOTER STEEL |
| | WILL NOT BE REQUIRED TO BE PART OF THE |
| | GROUNDING ELECTRODE SYSTEM UNLESS A STUB |
| | OUT IS ALREADY PROVIDED. IT IS NOT THE |
| | INTENTION TO AFFECT THE STRUCTURAL |
| | INTEGRITY OF THE EXISTING FOOTER. |
| | ** PLEASE SEE ORIG PLANS WERE REDLINED |
| | FOR THE "EQUIPMENT GROUNDING CONDUCTOR" |
| | SHOWN BEING INSTALLED FROM FPL TO THE |
| | MSB MAIN, HOWEVER WAS NOT SPECIFICALLY |
| | TYPE IN NOTES. PLEASE SEE 250.24B, |
| | 250.6, THE "EQUIPMENT GROUNDING |
| | CONDUCTOR" IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLASE SEE NO GROUNDING ELECTRODE SYSTEM |
| | WAS SHOWN. PLEASE SUBMIT A COMPLETE |
| | DETAIL PER 250.50, 250.52 ETC. |
| | PLEASE ALSO INDICATE THE ATTACHMENT |
| | LOCATIONS FOR THE TRANSFORMER PER |
| | 250.30,250.66 |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE:OK. |
| | ** ONLY A NOTE ** |
| | PLEASE SEE RATINGS ON SUB PANELS/BRNACH |
| | BRKRS ARE STILL BEING SHOWN 65K, ONLY |
| | ONE PANEL WAS REVISED FOR A 35K RATING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE AIC RATING |
| | FOR ALL SERVICE EQUIPMENT. PLEASE SEE |
| | TWO DIFFERENT RATINGS ARE SHOWN FOR MSB. |
| | PLEASE ALSO CLARIFY THE 65K RAITNGS |
| | INDICATE DFOR PANELS,AS THIS SEEMS HIGH, |
| | HOWEVER THIS IS PERMITTED. PLEASE |
| | INDICATE THE RATINGS OF THE BRANCH |
| | BRKRS. |
| | |
| | 12) NOTE: OK. |
| | |
| | |
| | ** PLEASE KNOW, A DETAILED RESPONSE TYPE |
| | WRITTEN LTR FROM THE DESIGN PROFESSIONAL |
| | WILL HELP IN THE REVIEW PROCESS WHEN |
| | RESUBMITTING PLANS. |
| | |
| | ** PLEASE ALSO KNOW, WHEN RESUBMITTING |
| | PLANS, ALL OLD/VOIDED SHEETS MUST BE |
| | COMPLETELY REMOVED FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. PLEASE |
| | KNOW, ONE COPY OF THE OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED WITH THE |
| | RESUBMITTED PLANS. |
| | |
| | ** PLEASE BE SURE TO SEE ANY OTHER |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THISOFFICE. |
| | |