Notes
Date Text
2006-07-16 00:00:00********* UNSAT2ND REVIEW *********
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1) NOTE: NO, PLEASE SEE RESPONSE
 MENTIONS THIS IS COMPLIED WITH, HOWEVER
 PLANS DO NOT INDICATE ANY SYSTEM FOR THE
 FIRST FLOOR OR 2NF FLR AS EACH FLR SHALL
 BE SEAPARATE. PLEASE SEE MOST ROOMS
 WHICH ARE CONSIDERED "SEPARATE SPCES"
 WITH FLOOR TO CEILING HEIGHT PARTITIONS
 ALSO REQUIRE SEPARATE CONTROLS WHICH
 WOULD OVER RIDE ANY TIME OF DAY
 SCHEDULEING ETC. PLEASE ALSO SEE OVER
 RIDE DEVICE LOCATIONS ARE REQUIRED TO BE
 SHOWN ON PLANS AT LOCATIONS AT THE PINT
 OF ENTRANCE(S) TO SPACE(S)AND HAVE
 VISABILITY OF LIGHTING IN WHICH THE OVER
 RIDE DEVICE CONTROLS.
 COULD NOT LOCATE THE VOLTAGE DROP WORST
 CASE FOR LONGER RUNS, (SITE LIGHTING)?
 PLEASE CLARIFY THE LIGHTING POWER
 DENSITIES (LPD). THE ENERGY CALCS SEEM
 TO INDICATE LIGHTING POWER DESIGN AT
 18,688 AND 23,760 ALLOWED, PLEASE
 CLARIFY THE LPD USED. PLEASE ALSO SEE
 CONTROLS MENTIONS MANUAL ON/OFF??
 PLEASE SEE 13-415.1.ABC.1.1, .1.2,.1.3,
 13-415.1.AB.1,13-415.1.ABC.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE COMING IN
 UNDER THE 2004 FBC. PLEASE SEE CHAPTER
 13, 13-413.1ABC.1. FOR VOLTAGE DROP
 CALCS TO BE PROVIDED FOR WORST CASE
 SCENERIO.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3,
 PLEASE PROVIDE ALL INFORMATION FOR
 LIGHTING CONTROL SYSTEM, TIME OF DAY,
 TYOE OF DEVICES, SYSTEMS ETC.
 INDICATE THE SECTION(S) AND PLEASE SEE
 MULTIPLE FLOOR REQUIREMENTS FOR
 ADDTIONAL CONTROLS.
 PLEASE SEE 13-413.1.ABC.2.2
 PLESASE SEE 13-415.1.ABC.3
  
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THIS WAS ONLY
 CHANGED ON "A" SHEETS. PLEAS KNOW, DUE
 TO REVISIONS ON ELECTRICAL SHEETSWHICH
 SOME WERE REVISED AND SOME WERE NOT,
 PLEASE BE SURE TO CHANGE THE DOOR SWING.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MAIN ELECTRICAL ROOM
 DOOR SHALL OPEN OUTWARD AND BE EQUIPPED
 WITH PANIC HARDWARE.
 110.26
  
 4) NOTE: OK, REVISED FIX TYPE.
  
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: NO/YES, PLEASE SEE RISER STILL
 ONLY MENTIONS IN NOTES THAT THE
 GROUNDING ELECTRODE SYSTEM PER NEC AND
 NOTE FOR TRANSFORMER ALSO MENTIONS PER
 NEC. PLEASE SEE THESE NOTES SHOULD
 REFERENCE THE DETAILS ON 7-1. PLEASE
 REVISE NOTES.
 PLEASE ALSO KNOW, EXISTING FOOTER STEEL
 WILL NOT BE REQUIRED TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM UNLESS A STUB
 OUT IS ALREADY PROVIDED. IT IS NOT THE
 INTENTION TO AFFECT THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTER.
 ** PLEASE SEE ORIG PLANS WERE REDLINED
 FOR THE "EQUIPMENT GROUNDING CONDUCTOR"
 SHOWN BEING INSTALLED FROM FPL TO THE
 MSB MAIN, HOWEVER WAS NOT SPECIFICALLY
 TYPE IN NOTES. PLEASE SEE 250.24B,
 250.6, THE "EQUIPMENT GROUNDING
 CONDUCTOR" IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 ** PREVIOUS REVIEW NOTE **
 PLASE SEE NO GROUNDING ELECTRODE SYSTEM
 WAS SHOWN. PLEASE SUBMIT A COMPLETE
 DETAIL PER 250.50, 250.52 ETC.
 PLEASE ALSO INDICATE THE ATTACHMENT
 LOCATIONS FOR THE TRANSFORMER PER
 250.30,250.66
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE:OK.
 ** ONLY A NOTE **
 PLEASE SEE RATINGS ON SUB PANELS/BRNACH
 BRKRS ARE STILL BEING SHOWN 65K, ONLY
 ONE PANEL WAS REVISED FOR A 35K RATING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE AIC RATING
 FOR ALL SERVICE EQUIPMENT. PLEASE SEE
 TWO DIFFERENT RATINGS ARE SHOWN FOR MSB.
 PLEASE ALSO CLARIFY THE 65K RAITNGS
 INDICATE DFOR PANELS,AS THIS SEEMS HIGH,
 HOWEVER THIS IS PERMITTED. PLEASE
 INDICATE THE RATINGS OF THE BRANCH
 BRKRS.
  
 12) NOTE: OK.
  
  
 ** PLEASE KNOW, A DETAILED RESPONSE TYPE
 WRITTEN LTR FROM THE DESIGN PROFESSIONAL
 WILL HELP IN THE REVIEW PROCESS WHEN
 RESUBMITTING PLANS.
  
 ** PLEASE ALSO KNOW, WHEN RESUBMITTING
 PLANS, ALL OLD/VOIDED SHEETS MUST BE
 COMPLETELY REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE
 KNOW, ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED WITH THE
 RESUBMITTED PLANS.
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THISOFFICE.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW.