| 2006-08-11 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ITEMS FROM PREVIOUS LIST NEEDING FURTHER |
| | CLARIFICATION; NUMBERING REMAINING THE |
| | SAME FOR CONSISTENCY: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)REGARDING IMPACT FEES, THE PLANS |
| | WERE STAMPED WITH INTERIOR ALTERATION, 0 |
| | SQUARE FEET.THIS IS IN CONFLICT WITH |
| | LS1 WHICH SHOWS AN ADDITION OF 1000 SF. |
| | THIS |
| | SHOULD STATE WHETHER THIS IS HABITABLE |
| | SPACE OR NOT.THE LOADING DOCK |
| | ENCLOSURE AND THE ENTRY ROOFS SHOULD BE |
| | DECLARED SEPARATELY AS IMPACT FEES WILL |
| | BE DUE ON THE LOADING DOCK RENOVATION |
| | BUT NOT ON THE ENTRIES IF THEY ARE NOT |
| | UNDER AIR. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.)THE DUMPSTER ENCLOSURES WILL |
| | REQUIRE A SEPARATE PERMIT.COMPLETE A |
| | PERMIT APPLICATION.SEPARATE PLANS ARE |
| | NOT REQUIRED. |
| | |
| | 5.)SEPARATE PERMIT REQUIRED FOR THE |
| | FENCES.SUBMIT SEPARATELY WITH PLANS. |
| | THIS ITEM DOES NOT NEED TO BE ADDRESSED |
| | PRIOR TO ISSUANCE OF THIS PERMIT, BUT |
| | MUST BE ADDRESSED PRIOR TO COMMENCEMENT |
| | OF THE FENCING WORK.INFORMATIONAL |
| | ONLY. |
| | |
| | 6-7.)ADDRESSED. |
| | |
| | 8.)RAMP DETAIL 3-SP2 WAS REVISED TO |
| | SHOW 72IN, FBC11-4.8.4(2), PLEASE ALSO |
| | REVISE 01SP2.MY APOLOGIES FOR MISSING |
| | THIS DETAIL THE FIRST REVIEW. |
| | |
| | 9.)CATCH BASIN GRATINGS SHOWN ON |
| | THE NEW RAMP PLAN, 01-SP2 IS TO COMPLY |
| | WITH FBC11-4.5.4. |
| | |
| | 10-13.) |
| | |
| | 14.)THE PLAN SHOWS ACCORDION SHUTTERS |
| | ON THE SECOND FLOOR.THIS MUST BE |
| | APPROVED BY THE BUILDING OFFICIAL, ITEM |
| | #14 OF THE MISSILE IMPACT PROTECTION |
| | STANDARD, ATTACHED.SUBMIT AN |
| | INSTALLATION PLAN AS REFERENCED IN ITEM |
| | #13. |
| | |
| | THE PLAN SUBMITTED BY EMAIL IS TO BE |
| | SUBMITTED AS A SIGNED ORIGINAL FOR |
| | REVIEW BY THE BUILDING OFFICIAL.THIS |
| | MUST BE DONE PRIOR TO PERMIT ISSUANCE. |
| | |
| | 15.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DOR, FBC*106.3.3.SOME ARE |
| | REFERENCED SPECIFICALLY ON THE PLAN |
| | (SUCH AS ON A8-1), BUT OTHERS (SUCH AS |
| | THE ROOF PRODUCTS) ARE NOT.FOR |
| | PRODUCTS NOT REFERENCED BY NOA NUMBER ON |
| | THE PLAN, PLEASE REVIEW AND SHOW |
| | COMPLIANCE EITHER BY LETTER OR BY A |
| | REVIEW STAMP.THE RESPONSE LETTER |
| | STATED THAT THE PRODUCTS WERE REVIEWED |
| | BUT PLEASE PROVIDE EITHER A LETTER OR |
| | REVIEW STAMP. |
| | |
| | 16.)FROM PREVIOUS LIST, SAME PAPERWORK |
| | SUBMITTED WITH NO CHANGES: |
| | |
| | FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED, FAC9B72.IF A |
| | FLORIDA STATE PRODUCT APPROVAL IS NOT |
| | AVAILABLE, AND YOU HAVE SUBMITTED A NOA, |
| | PLEASE ADVISE AND A LOCAL PRODUCT |
| | APPROVAL WILL BE ISSUED. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | STOREFRONT SYSTEM >10',NOA 01-0228.09 |
| | IS EXPIRED.ALSO THIS REQUIRES A |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL. |
| | THE NOA MUST BE CURRENT FOR A LOCAL TO |
| | BE ISSUED FROM THE NOA.A LOCAL PRODUCT |
| | APPROVAL CAN BE ISSUED WITH EITHER A |
| | TEST OR EVALUATION REPORT, PLEASE READ |
| | FAC9B72. |
| | |
| | STOREFRONT SYSTEM < 10', FLORIDA STATE |
| | PRODUCT APPROVAL 5844 WAS SUBMITTED. |
| | SUBMIT THE NOA REFERENCED ON THE STATE |
| | APPROVAL FOR VERIFICATION OF DESIGN |
| | PRESSURES AND FOR INSTALLATION |
| | INSTRUCTIONS IN THE FIELD.NOTE THE |
| | PRODUCT LIMITATION THAT PRESSURES ARE TO |
| | BE DIVIDED BY 1.33 OR VERIFIED BY A |
| | FLORIDA PE. |
| | |
| | CECO DOOR, A NOA WAS PROVIDED.A LOCAL |
| | PRODUCT APPROVAL HAS ALREADY BEEN ISSUED |
| | FOR THIS PRODUCT.PLEASE HAVE DOR |
| | REVIEW. |
| | |
| | ACCORDION SHUTTER, REQUIRES DOR REVIEW |
| | AND BACKUP AND NOA REFERENCED IN THE |
| | FLORIDA STATE PRODUCT APPROVAL.CIRCLE |
| | THE DETAILS WHICH APPLY TO THIS |
| | INSTALLATION.SHOW ANCHORING SPACING. |
| | THIS CAN BE DONE BY EITHER COMPLETING A |
| | SCHEDULE SUCH AS THE SAMPLE FORM |
| | ATTACHED OR BY CIRCLING IT ON THE |
| | PRODUCT APPROVAL. |
| | |
| | STOREFRONT DOOR, THE NOA PROVIDED AND |
| | REFERENCED ON A8-1 IS NON IMPACT.THE |
| | PLANS STATE IMPACT.ADDRESS.THE SHEET |
| | PROVIDED IS NOT A FLORIDA STATE PRODUCT |
| | APPROVAL, IT IS THE SEARCH RESULT. |
| | PROVIDE THE FLORIDA STATE PRODUCT |
| | APPROVAL.SEE THE OTHERS SUBMITTED AS |
| | THE OTHERS WERE PRINTED PROPERLY. |
| | |
| | LOUVER, PROVIDE FLORIDA STATE PRODUCT |
| | APPROVAL.IF ONE IS NOT AVAILABLE, A |
| | LOCAL WILL BE ISSUED USING THE NOA. |
| | |
| | NO PRODUCT APPROVALS FOR THE ROOF WERE |
| | SUBMITTED.THEY MAY BE SUBMITTED WITH |
| | THE ROOF PERMIT APPLICATION, BUT |
| | SEPARATE FEES BASED ON VALUE WILL BE |
| | CHARGED. |
| | |
| | ALL ITEMS APPEAR CODE COMPLIANT, BUT |
| | PLEASE SUBMIT ALL PAPERWORK AS |
| | REQUESTED. |
| | |
| | 17.)FROM PREVIOUS LIST, THE ENERGY |
| | CALCS DIFFER IN SQUARE |
| | FOOTAGE, 20550 ON THE ENERGY CALC, 23000 |
| | ON LS1.CLARIFY THE |
| | DISCREPANCY. YOUR RESPONSE THAT THE |
| | DISCREPANCY IS DUE TO WHERE THE ROOMS |
| | WERE MEASURED IS NOTED, BUT THEY SHOULD |
| | BE MEASURED FROM OUTSIDE WALLS FBC 13-2, |
| | DEFINITIONS, CONDITIONED FLOOR AREA, |
| | GROSS FLOOR AREA, FLOOR AREA. |
| | |
| | 18.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS, FBC13-103.1. |
| | |
| | 19.)ADDITIONAL FEES DUE, SEE ATTACHED |
| | (RADON, FS404.056, FS166.021. |
| | |