Plan Review Notes
Plan Review Notes For Permit 06031357
Permit Number 06031357
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ITEMS FROM PREVIOUS LIST NEEDING FURTHER
 CLARIFICATION; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)REGARDING IMPACT FEES, THE PLANS
 WERE STAMPED WITH INTERIOR ALTERATION, 0
 SQUARE FEET.THIS IS IN CONFLICT WITH
 LS1 WHICH SHOWS AN ADDITION OF 1000 SF.
 THIS
 SHOULD STATE WHETHER THIS IS HABITABLE
 SPACE OR NOT.THE LOADING DOCK
 ENCLOSURE AND THE ENTRY ROOFS SHOULD BE
 DECLARED SEPARATELY AS IMPACT FEES WILL
 BE DUE ON THE LOADING DOCK RENOVATION
 BUT NOT ON THE ENTRIES IF THEY ARE NOT
 UNDER AIR.
  
 3.)ADDRESSED.
  
 4.)THE DUMPSTER ENCLOSURES WILL
 REQUIRE A SEPARATE PERMIT.COMPLETE A
 PERMIT APPLICATION.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 FENCES.SUBMIT SEPARATELY WITH PLANS.
 THIS ITEM DOES NOT NEED TO BE ADDRESSED
 PRIOR TO ISSUANCE OF THIS PERMIT, BUT
 MUST BE ADDRESSED PRIOR TO COMMENCEMENT
 OF THE FENCING WORK.INFORMATIONAL
 ONLY.
  
 6-7.)ADDRESSED.
  
 8.)RAMP DETAIL 3-SP2 WAS REVISED TO
 SHOW 72IN, FBC11-4.8.4(2), PLEASE ALSO
 REVISE 01SP2.MY APOLOGIES FOR MISSING
 THIS DETAIL THE FIRST REVIEW.
  
 9.)CATCH BASIN GRATINGS SHOWN ON
 THE NEW RAMP PLAN, 01-SP2 IS TO COMPLY
 WITH FBC11-4.5.4.
  
 10-13.)
  
 14.)THE PLAN SHOWS ACCORDION SHUTTERS
 ON THE SECOND FLOOR.THIS MUST BE
 APPROVED BY THE BUILDING OFFICIAL, ITEM
 #14 OF THE MISSILE IMPACT PROTECTION
 STANDARD, ATTACHED.SUBMIT AN
 INSTALLATION PLAN AS REFERENCED IN ITEM
 #13.
  
 THE PLAN SUBMITTED BY EMAIL IS TO BE
 SUBMITTED AS A SIGNED ORIGINAL FOR
 REVIEW BY THE BUILDING OFFICIAL.THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.
  
 15.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DOR, FBC*106.3.3.SOME ARE
 REFERENCED SPECIFICALLY ON THE PLAN
 (SUCH AS ON A8-1), BUT OTHERS (SUCH AS
 THE ROOF PRODUCTS) ARE NOT.FOR
 PRODUCTS NOT REFERENCED BY NOA NUMBER ON
 THE PLAN, PLEASE REVIEW AND SHOW
 COMPLIANCE EITHER BY LETTER OR BY A
 REVIEW STAMP.THE RESPONSE LETTER
 STATED THAT THE PRODUCTS WERE REVIEWED
 BUT PLEASE PROVIDE EITHER A LETTER OR
 REVIEW STAMP.
  
 16.)FROM PREVIOUS LIST, SAME PAPERWORK
 SUBMITTED WITH NO CHANGES:
  
 FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, AND YOU HAVE SUBMITTED A NOA,
 PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED.
 WWW.FLORIDABUILDING.ORG
  
 STOREFRONT SYSTEM >10',NOA 01-0228.09
 IS EXPIRED.ALSO THIS REQUIRES A
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
 THE NOA MUST BE CURRENT FOR A LOCAL TO
 BE ISSUED FROM THE NOA.A LOCAL PRODUCT
 APPROVAL CAN BE ISSUED WITH EITHER A
 TEST OR EVALUATION REPORT, PLEASE READ
 FAC9B72.
  
 STOREFRONT SYSTEM < 10', FLORIDA STATE
 PRODUCT APPROVAL 5844 WAS SUBMITTED.
 SUBMIT THE NOA REFERENCED ON THE STATE
 APPROVAL FOR VERIFICATION OF DESIGN
 PRESSURES AND FOR INSTALLATION
 INSTRUCTIONS IN THE FIELD.NOTE THE
 PRODUCT LIMITATION THAT PRESSURES ARE TO
 BE DIVIDED BY 1.33 OR VERIFIED BY A
 FLORIDA PE.
  
 CECO DOOR, A NOA WAS PROVIDED.A LOCAL
 PRODUCT APPROVAL HAS ALREADY BEEN ISSUED
 FOR THIS PRODUCT.PLEASE HAVE DOR
 REVIEW.
  
 ACCORDION SHUTTER, REQUIRES DOR REVIEW
 AND BACKUP AND NOA REFERENCED IN THE
 FLORIDA STATE PRODUCT APPROVAL.CIRCLE
 THE DETAILS WHICH APPLY TO THIS
 INSTALLATION.SHOW ANCHORING SPACING.
 THIS CAN BE DONE BY EITHER COMPLETING A
 SCHEDULE SUCH AS THE SAMPLE FORM
 ATTACHED OR BY CIRCLING IT ON THE
 PRODUCT APPROVAL.
  
 STOREFRONT DOOR, THE NOA PROVIDED AND
 REFERENCED ON A8-1 IS NON IMPACT.THE
 PLANS STATE IMPACT.ADDRESS.THE SHEET
 PROVIDED IS NOT A FLORIDA STATE PRODUCT
 APPROVAL, IT IS THE SEARCH RESULT.
 PROVIDE THE FLORIDA STATE PRODUCT
 APPROVAL.SEE THE OTHERS SUBMITTED AS
 THE OTHERS WERE PRINTED PROPERLY.
  
 LOUVER, PROVIDE FLORIDA STATE PRODUCT
 APPROVAL.IF ONE IS NOT AVAILABLE, A
 LOCAL WILL BE ISSUED USING THE NOA.
  
 NO PRODUCT APPROVALS FOR THE ROOF WERE
 SUBMITTED.THEY MAY BE SUBMITTED WITH
 THE ROOF PERMIT APPLICATION, BUT
 SEPARATE FEES BASED ON VALUE WILL BE
 CHARGED.
  
 ALL ITEMS APPEAR CODE COMPLIANT, BUT
 PLEASE SUBMIT ALL PAPERWORK AS
 REQUESTED.
  
 17.)FROM PREVIOUS LIST, THE ENERGY
 CALCS DIFFER IN SQUARE
 FOOTAGE, 20550 ON THE ENERGY CALC, 23000
 ON LS1.CLARIFY THE
 DISCREPANCY. YOUR RESPONSE THAT THE
 DISCREPANCY IS DUE TO WHERE THE ROOMS
 WERE MEASURED IS NOTED, BUT THEY SHOULD
 BE MEASURED FROM OUTSIDE WALLS FBC 13-2,
 DEFINITIONS, CONDITIONED FLOOR AREA,
 GROSS FLOOR AREA, FLOOR AREA.
  
 18.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 19.)ADDITIONAL FEES DUE, SEE ATTACHED
 (RADON, FS404.056, FS166.021.
  