Plan Review Notes
Plan Review Notes For Permit 06031357
Permit Number 06031357
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-03 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SURVEY SHEET 1 OF 1 PER FS 472.025
 ALL FINAL DRAWINGS, PLANS ETC. PREPARED
 BY THE REGISTRANT SHALL BE SIGNED,
 SEALED, AND DATED BY THE RESISTRANT.
  
 2. SHT D-1 KEY NOTES #8, IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5.
  
 3. SHT A2.1 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS AS
 REQUIRED IN SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS. SHOW THE SF OF EACH
 AREA BEING DRAINED, ALONG WITH 1/2 THE
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND SHOW THE AREAS OF ROOFS
 THAT DRAIN ONTO THE ROOF AREAS FROM
 ABOVE IN CLACULATIONS. - IT APPEARS THAT
 NEW AREA WILL BE ADDED TO THE ROOF AREAS
 IN THE FORM OF NEW ROOF/WALL AREAS AT
 ENTRANCES.
  
 4. SHT A2.1 THE NEW OVERFLOW SCUPPERS
 SIZING CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE INDICATE THAT SCUPPERS WERE SIZED
 TO COMPLY WITH SECTIONS 1101.7, 1107.3 &
 TABLE 1106.7.
  
 5. SHT A6-1 THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE WITH
 ACCESSIBILITY:
 FOR DRINKING FOUNTAINS:
 A. 11-4.15.5 CLEAR FLOOR SPACE
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.6 DISPENSERS
 FOR TOILET STALLS:
 A. 11-4.17.3 (EXCEPTION) LAV SHALL BE
 LOCATED 60" OFF W/C WALL TO SIDE OF THE
 FIXTURE PER FIGURE 30E. IT SCALES OUT TO
 BE APPROXIMATELY 58".
 FOR URINALS:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR LAVX:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR THE TOILET ROOMS:
 A. 11-4.22.3 UNOBSTRUCTED TURNING IN
 TOILET ROOM. (NOT IN STALLS).
  
 6. SHT A9.4 DETAILS 03, 04, 05, & 06
 SHOW THE FOLLOWING TO SHOW COMPLIANCE:
  
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 7. SHT P1-1 DEAD ENDS. KEY NOTES 1,3,& 5
 INDICATE LINE TO BE FLUSH TO FLOOR.
 BRANCH LINE PIPES TO BE REMOVED TO
 BUILDING DRAIN AND CAPPED. CAP SHALL NOT
 BE COVERED UNTIL INSPECTED BY FIELD
 INSPECTOR. SECTION 704.5.
  
 8. SHT P2-1 DEFINITION OF DEAD END - 2'
 OR MORE OF ABANDONED PIPE. DEAD ENDS ARE
 SHOWN, (IN LECTURE HALL, SANT. AND
 STORM). PLEASE REMOVE ALL DEAD ENDS.
 SECTION 704.5.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]