| Date |
Text |
| 2006-06-07 00:00:00 | ***DENIED*** |
| | |
| | 1) PLEASE PROVIDE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS IN ACCORDANCE WITH NFPA 101, |
| | CHAPTER 10. |
| | |
| | 2) IN ADDITION TO FIRE SPRINKLER, |
| | SEPARATE SHOP DRAWINGS AND PERMIT |
| | REQUIRED FOR FIRE ALARM REMODEL. |
| | |
| | 3) RAMPS TO COMPLY WITH APPLICABLE |
| | BUILDING CODES, AND NFPA 101, SECTION |
| | 7.2.5. |
| | |
| | 4) PLEASE CLARIFY THE OCCUPANT LOAD FOR |
| | LECTURE HALL. USING THE CONCENTRATED |
| | FACTOR, IT WOULD APPEAR WILL NOT SUPPORT |
| | THE SEATING ILLUSTRATION. |
| | |
| | 5) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 6) KNOX BOX APPLICATION CAN BE OBTAINED |
| | AT THE BUREAU OF FIRE PREVENTION. |
| | |
| | 7) PLEASE SHOW ADDRESS ON BUILDING, NEW |
| | OR EXISTING THAT SHALL BE MINIMUM OF 6" |
| | IN HEIGHT AND CONTRASTING TO BACKGROUND. |
| | |
| | |
| | 8) WILL CARD ACCESS SYSTEM IMPACT |
| | REQUIRED MEANS OF EGRESS? |
| | |
| | 9) EMERGENCY LIGHT BACK UP SYSTEMS SHALL |
| | BE MAINTAINED FOR MINIMUM OF 90 MINUTES. |
| | |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |