2006-05-17 00:00:00IN ELEC FOR REVIEW.
 ********* UNSAT ***********
  
 1) NOTE: PLEASE SEE PLANS ARE COMING IN
 UNDER THE 2004 FBC. PLEASE SEE CHAPTER
 13, 13-413.1ABC.1. FOR VOLTAGE DROP
 CALCS TO BE PROVIDED FOR WORST CASE
 SCENERIO.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3,
 PLEASE PROVIDE ALL INFORMATION FOR
 LIGHTING CONTROL SYSTEM, TIME OF DAY,
 TYOE OF DEVICES, SYSTEMS ETC.
 INDICATE THE SECTION(S) AND PLEASE SEE
 MULTIPLE FLOOR REQUIREMENTS FOR
 ADDTIONAL CONTROLS.
 PLEASE SEE 13-413.1.ABC.2.2
 PLESASE SEE 13-415.1.ABC.3
  
  
 2) NOTE: PLEASE CORRELATE EXITING, AND
 EGRESS PATHS LTS WITH FIXTURE SCHEDULE
 AS SOME FIXTURES DO NOT CONTAIN BATTEY
 BACK UP WHERE REQUIRED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2,
 WHERE STAIRS ARE NOW REQUIRED TO HAVE
 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EM CONDITIONS. PLEASE PROVIDE
 COMPLETE PHOTOMETRICS FOR ALL EGRESS
 PATHS. PLEASEKNOW, THE STAIRS CAN BE A
 "TYPICAL DETAIL". ONE SHWOING NORMAL,
 ONE SHOWING EM.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS AS
 ONE TYPE OF FIXTURE SEEMS TO SHOW ONLY
 30 MIN??
  
 3) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 DOOR SHALL OPEN OUTWARD AND BE EQUIPPED
 WITH PANICA HARDWARE.
 110.26
  
 4) NOTE: PLEASE SEE THE MAIN ELECTRICAL
 ROOM WILL BE REQUIRED TO CONTAIN A MIN
 OF ONE BATTERY BACK UP TYPE OF FIXTURE.
 700.16, 7.8,7.8
  
 5) NOTE: PLEASE SEE MISSING RECEPT PER
 210.63, 210.8 FOR A/C EQUIPMENT
  
 6) NOTE: PLEASE SEE 620.23, 620.24, AS
 ELEVATOR EQUIPMENT RMS AND ELEV SHALL
 HAVE DEDICATED CIRCUITS AS REQUIRED.
 PLEASE SEE SOME OF THESE ITEMS ARE SHOWN
 CIRCUITED TO STAIR LTS??
  
 7) NOTE: PELASE SEE NO GROUNDING
 ELECTRODE SYSTEM WAS SHOWN. PLEASE
 SUBMIT A COMPLETE DETAIL PER
 250.50,250.52 ETC.
 PLEASE ALSO INDICATE THE ATTACHMENT
 LOCATIONS FOR THE TRANSFORMER PER
 250.30,250.66
  
 8) NOTE: PLEASE TYPE AND USE OF THE
 TRANSFORMER AS RISER INDICATE THIS BEING
 USED FROM 120/208V 3-PHASE TO 120/208V
 3-PHASE??
  
 9) NOTE: PLEASE SEE MSB IS SHOWN AS
 "GFI" PROTECTED?? PLEASE KNOW, IF
 MEETING THE REQUIREMENTS OF
 230.95,240.13 ETC, THIS WOULD BE GF
 PROTECTED. "GFI" IS FOR PERSONNEL.
 PLEASE CLARIFY THE GF PROTECION AS THIS
 IS SHOWN AS 120/208V??
  
 10) NOTE: PLEASE VERIFY MAIN FOR MSB.
 PLEASE SEE ONE END OF THIS EQUIPMENT IS
 SHOWN AS MLO, INDICATE MORE THAN 6
 SPACES AND 6 MAINS. 230.70,230.71??
 PLEASE SEE THE OTHER SEEMS TO INDICATE A
 MCB BUT THIS IS UNCLEAR. PLEASE NOTE AND
 INDICATE THIS MCB, CONTAINING A MANUAL
 MEANS OF DISCONNECT LOCATED ON THE
 OUTSIDE OF THIS EQUIPMENT, RATED FOR THE
 LOAD SERVED PER 230.76,230.79
  
 11) NOTE: PLEASE SUBMIT THE AIC RATING
 FOR ALL SERVICE EQUIPMENT. PLEASE SEE
 TWO DIFFERENT RATINGS ARE SHOWN FOR MSB.
 PLEASE ALSO CLARIFY THE 65K RAITNGS
 INDICATE DFOR PANELS,AS THIS SEEMS HIGH,
 HOWEVER THIS IS PERMITTED. PLEASE
 INDICATE THE RATINGS OF THE BRANCH
 BRKRS.
  
 12) NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR LT POLES TO MEET FBC
 140.
  
 ** PLEASE KNOW, A DETAILED RESPONSE TYPE
 WRITTEN LTR FROM THE DESIGN PROFESSIONAL
 WILL HELP IN THE REVIEW PROCESS WHEN
 RESUBMITTING PLANS.
  
 ** PLEASE ALSO KNOW, WHEN RESUBMITTING
 PLANS, ALL OLD/VOIDED SHEETS MUST BE
 COMPLETELY REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE
 KNOW, ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED WITH THE
 RESUBMITTED PLANS.
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THISOFFICE.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW.