| 2006-05-17 00:00:00 | IN ELEC FOR REVIEW. |
| | ********* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE PLANS ARE COMING IN |
| | UNDER THE 2004 FBC. PLEASE SEE CHAPTER |
| | 13, 13-413.1ABC.1. FOR VOLTAGE DROP |
| | CALCS TO BE PROVIDED FOR WORST CASE |
| | SCENERIO. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, |
| | PLEASE PROVIDE ALL INFORMATION FOR |
| | LIGHTING CONTROL SYSTEM, TIME OF DAY, |
| | TYOE OF DEVICES, SYSTEMS ETC. |
| | INDICATE THE SECTION(S) AND PLEASE SEE |
| | MULTIPLE FLOOR REQUIREMENTS FOR |
| | ADDTIONAL CONTROLS. |
| | PLEASE SEE 13-413.1.ABC.2.2 |
| | PLESASE SEE 13-415.1.ABC.3 |
| | |
| | |
| | 2) NOTE: PLEASE CORRELATE EXITING, AND |
| | EGRESS PATHS LTS WITH FIXTURE SCHEDULE |
| | AS SOME FIXTURES DO NOT CONTAIN BATTEY |
| | BACK UP WHERE REQUIRED. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2, |
| | WHERE STAIRS ARE NOW REQUIRED TO HAVE |
| | 10FT CANDLES UNDER NORMAL AND 1FT CANDLE |
| | UNDER EM CONDITIONS. PLEASE PROVIDE |
| | COMPLETE PHOTOMETRICS FOR ALL EGRESS |
| | PATHS. PLEASEKNOW, THE STAIRS CAN BE A |
| | "TYPICAL DETAIL". ONE SHWOING NORMAL, |
| | ONE SHOWING EM. |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS AS |
| | ONE TYPE OF FIXTURE SEEMS TO SHOW ONLY |
| | 30 MIN?? |
| | |
| | 3) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| | DOOR SHALL OPEN OUTWARD AND BE EQUIPPED |
| | WITH PANICA HARDWARE. |
| | 110.26 |
| | |
| | 4) NOTE: PLEASE SEE THE MAIN ELECTRICAL |
| | ROOM WILL BE REQUIRED TO CONTAIN A MIN |
| | OF ONE BATTERY BACK UP TYPE OF FIXTURE. |
| | 700.16, 7.8,7.8 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.63, 210.8 FOR A/C EQUIPMENT |
| | |
| | 6) NOTE: PLEASE SEE 620.23, 620.24, AS |
| | ELEVATOR EQUIPMENT RMS AND ELEV SHALL |
| | HAVE DEDICATED CIRCUITS AS REQUIRED. |
| | PLEASE SEE SOME OF THESE ITEMS ARE SHOWN |
| | CIRCUITED TO STAIR LTS?? |
| | |
| | 7) NOTE: PELASE SEE NO GROUNDING |
| | ELECTRODE SYSTEM WAS SHOWN. PLEASE |
| | SUBMIT A COMPLETE DETAIL PER |
| | 250.50,250.52 ETC. |
| | PLEASE ALSO INDICATE THE ATTACHMENT |
| | LOCATIONS FOR THE TRANSFORMER PER |
| | 250.30,250.66 |
| | |
| | 8) NOTE: PLEASE TYPE AND USE OF THE |
| | TRANSFORMER AS RISER INDICATE THIS BEING |
| | USED FROM 120/208V 3-PHASE TO 120/208V |
| | 3-PHASE?? |
| | |
| | 9) NOTE: PLEASE SEE MSB IS SHOWN AS |
| | "GFI" PROTECTED?? PLEASE KNOW, IF |
| | MEETING THE REQUIREMENTS OF |
| | 230.95,240.13 ETC, THIS WOULD BE GF |
| | PROTECTED. "GFI" IS FOR PERSONNEL. |
| | PLEASE CLARIFY THE GF PROTECION AS THIS |
| | IS SHOWN AS 120/208V?? |
| | |
| | 10) NOTE: PLEASE VERIFY MAIN FOR MSB. |
| | PLEASE SEE ONE END OF THIS EQUIPMENT IS |
| | SHOWN AS MLO, INDICATE MORE THAN 6 |
| | SPACES AND 6 MAINS. 230.70,230.71?? |
| | PLEASE SEE THE OTHER SEEMS TO INDICATE A |
| | MCB BUT THIS IS UNCLEAR. PLEASE NOTE AND |
| | INDICATE THIS MCB, CONTAINING A MANUAL |
| | MEANS OF DISCONNECT LOCATED ON THE |
| | OUTSIDE OF THIS EQUIPMENT, RATED FOR THE |
| | LOAD SERVED PER 230.76,230.79 |
| | |
| | 11) NOTE: PLEASE SUBMIT THE AIC RATING |
| | FOR ALL SERVICE EQUIPMENT. PLEASE SEE |
| | TWO DIFFERENT RATINGS ARE SHOWN FOR MSB. |
| | PLEASE ALSO CLARIFY THE 65K RAITNGS |
| | INDICATE DFOR PANELS,AS THIS SEEMS HIGH, |
| | HOWEVER THIS IS PERMITTED. PLEASE |
| | INDICATE THE RATINGS OF THE BRANCH |
| | BRKRS. |
| | |
| | 12) NOTE: PLEASE SUBMIT WIND LOAD |
| | CALCULATIONS FOR LT POLES TO MEET FBC |
| | 140. |
| | |
| | ** PLEASE KNOW, A DETAILED RESPONSE TYPE |
| | WRITTEN LTR FROM THE DESIGN PROFESSIONAL |
| | WILL HELP IN THE REVIEW PROCESS WHEN |
| | RESUBMITTING PLANS. |
| | |
| | ** PLEASE ALSO KNOW, WHEN RESUBMITTING |
| | PLANS, ALL OLD/VOIDED SHEETS MUST BE |
| | COMPLETELY REMOVED FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. PLEASE |
| | KNOW, ONE COPY OF THE OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED WITH THE |
| | RESUBMITTED PLANS. |
| | |
| | ** PLEASE BE SURE TO SEE ANY OTHER |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THISOFFICE. |
| | |