Plan Review Notes
Plan Review Notes For Permit 06031357
Permit Number 06031357
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025.THIS APPEARS TO
 BE A CHANGE OF OCCUPANCY, FROM BUSINESS
 TO ASSEMBLY, FOR A PORTION OF THE
 BUILDING.
  
 LS1 SHOWS AN ADDITION OF 1000 SF.THIS
 SHOULD STATE WHETHER THIS IS HABITABLE
 SPACE OR NOT, AND IF IT IS, WHICH
 OCCUPANCY.IT APPEARS THAT THE ADDITION
 IS ROOF AREA ONLY, WHICH WILL NOT BE
 CALCULATED FOR IMPACT FEES BUT WHICH
 MUST BE INCLUDED FOR TABLE 503
 COMPLIANCE.
  
 3.)THE ACCESSIBLE PARKING DETAIL C7 IS
 TO COMPLY WITH CITY OF WEST PALM BEACH
 STANDARDS, SEE ATTACHED.
  
 4.)THE DUMPSTER ENCLOSURES WILL
 REQUIRE A SEPARATE PERMIT.COMPLETE A
 PERMIT APPLICATION.SEPARATE PLANS ARE
 NOT REQUIRED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 FENCES.SUBMIT SEPARATELY WITH PLANS.
 THIS ITEM DOES NOT NEED TO BE ADDRESSED
 PRIOR TO ISSUANCE OF THIS PERMIT, BUT
 MUST BE ADDRESSED PRIOR TO COMMENCEMENT
 OF THE FENCING WORK.INFORMATIONAL
 ONLY.
  
 6.)SP1 REFERS TO MECHANICAL SHEET ???,
 PLEASE REVISE NOTE.
  
 7.)AN EXISTING ACCESSIBLE ROUTE FROM
 THE PUBLIC WAY IS SHOWN.SHOW THE WIDTH
 AND MAX SLOPE, EITHER WITH A NOTE ON THE
 PLAN OR WITH EXISTING ELEVATIONS, TO
 SHOW COMPLIANCE WITH FBC11-4.1.2(1) AND
 (2), FBC11-4.1.6(1)(B).
  
 8.)RAMP DETAIL 3-SP2 SHOWS 5FT AT THE
 BOTTOM OF THE RAMP.SEE FBC11-4.8.4(2),
 72IN REQUIRED.
  
 9.)WHAT IS THE "EXISTING CB" SHOWN ON
 THE NEW RAMP PLAN, 01-SP2?IT IS IN THE
 ACCESS AISLE FOR THE ACCESSIBLE PARKING
 SPACE.A SEARCH OF STANDARD
 ABBREVIATIONS WAS NOT HELPFUL.IF YOU
 USE NONSTANDARD ABBREVIATIONS, PLEASE
 INCLUDE A LEGEND.
  
 10.)LS1, APPLICABLE CODES, 8-A2-3, AND
 OTHER DETAILS REFER TO ASCE7-98.THIS
 SHOULD BE ASCE7-02, FBC35.
  
 11.)LS1 CODE SUMMARY REFERS TO TABLE
 500.THIS IS TABLE 503 IN THE NEW CODE.
  
 12.)LS1, PROVIDE CALCULATIONS FOR
 ALLOWABLE AREA INCREASES TO SHOW HOW YOU
 HAVE ARRIVED AT THE ALLOWABLE AREA.
 PLANS APPEAR CODE COMPLIANT BUT HOW YOU
 HAVE ARRIVED AT CODE COMPLIANCE SHOULD
 BE CLEAR.SEE ALSO FBC302.3.2.
  
 13.)LS3, SOUTH STAIR, DOORS DO NOT
 LEAD TO AN EXIT; ONE DOOR OPENS INTO
 WHAT APPEARS TO BE A CLOSET, AND THE
 OTHER DOOR OPENS INTO THE FIRST FLOOR
 SPACE.TRAVEL DISTANCE FROM SECOND
 FLOOR FOR SECOND MEANS OF EGRESS IS NOT
 CLEAR.
  
 14.)THE PLAN SHOWS ACCORDION SHUTTERS
 ON THE SECOND FLOOR.THIS MUST BE
 APPROVED BY THE BUILDING OFFICIAL, ITEM
 #14 OF THE MISSILE IMPACT PROTECTION
 STANDARD, ATTACHED.SUBMIT AN
 INSTALLATION PLAN AS REFERENCED IN ITEM
 #13.
  
 THE PLAN MAY BE SUBMITTED SEPARATELY
 FROM THE PERMIT APPLICATION RESUBMITTAL.
 FAILURE TO GET A PLAN APPROVED PRIOR TO
 RESUBMITTAL WILL RESULT IN DELAYS IN
 PERMIT ISSUANCE.
  
 THE INSTALLATION PLAN MAY BE SUBMITTED
 VIA EMAIL FOR PRELIMINARY REVIEW TO
 [email protected] PROVIDED ALL DOCUMENTATION
 IS LEGIBLE.A HARD COPY ORIGINAL SIGNED
 BY ALL PARTIES AFTER ALL COMMENTS HAVE
 BEEN ADDRESSED WILL BE REQUIRED FOR
 APPROVAL BY THE BUILDING OFFICIAL.
  
 15.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DOR, FBC*106.3.3.SOME ARE
 REFERENCED SPECIFICALLY ON THE PLAN
 (SUCH AS ON A8-1), BUT OTHERS (SUCH AS
 THE ROOF PRODUCTS) ARE NOT.FOR
 PRODUCTS NOT REFERENCED BY NOA NUMBER ON
 THE PLAN, PLEASE REVIEW AND SHOW
 COMPLIANCE EITHER BY LETTER OR BY A
 REVIEW STAMP.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, AND YOU HAVE SUBMITTED A NOA,
 PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED.
 WWW.FLORIDABUILDING.ORG
  
 STOREFRONT SYSTEM >10',NOA 01-0228.09
 IS EXPIRED.ALSO THIS REQUIRES A
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
 THE NOA MUST BE CURRENT FOR A LOCAL TO
 BE ISSUED FROM THE NOA.A LOCAL PRODUCT
 APPROVAL CAN BE ISSUED WITH EITHER A
 TEST OR EVALUATION REPORT, PLEASE READ
 FAC9B72.
  
 STOREFRONT SYSTEM < 10', FLORIDA STATE
 PRODUCT APPROVAL 5844 WAS SUBMITTED.
 SUBMIT THE NOA REFERENCED ON THE STATE
 APPROVAL FOR VERIFICATION OF DESIGN
 PRESSURES AND FOR INSTALLATION
 INSTRUCTIONS IN THE FIELD.NOTE THE
 PRODUCT LIMITATION THAT PRESSURES ARE TO
 BE DIVIDED BY 1.33 OR VERIFIED BY A
 FLORIDA PE.
  
 CECO DOOR, A NOA WAS PROVIDED.A LOCAL
 PRODUCT APPROVAL HAS ALREADY BEEN ISSUED
 FOR THIS PRODUCT.PLEASE HAVE DOR
 REVIEW.
  
 ACCORDION SHUTTER, REQUIRES DOR REVIEW
 AND BACKUP AND NOA REFERENCED IN THE
 FLORIDA STATE PRODUCT APPROVAL.CIRCLE
 THE DETAILS WHICH APPLY TO THIS
 INSTALLATION.SHOW ANCHORING SPACING.
 THIS CAN BE DONE BY EITHER COMPLETING A
 SCHEDULE SUCH AS THE SAMPLE FORM
 ATTACHED OR BY CIRCLING IT ON THE
 PRODUCT APPROVAL.
  
 STOREFRONT DOOR, THE NOA PROVIDED AND
 REFERENCED ON A8-1 IS NON IMPACT.THE
 PLANS STATE IMPACT.ADDRESS.THE SHEET
 PROVIDED IS NOT A FLORIDA STATE PRODUCT
 APPROVAL, IT IS THE SEARCH RESULT.
 PROVIDE THE FLORIDA STATE PRODUCT
 APPROVAL.SEE THE OTHERS SUBMITTED AS
 THE OTHERS WERE PRINTED PROPERLY.
  
 LOUVER, PROVIDE FLORIDA STATE PRODUCT
 APPROVAL.IF ONE IS NOT AVAILABLE, A
 LOCAL WILL BE ISSUED USING THE NOA.
  
 NO PRODUCT APPROVALS FOR THE ROOF WERE
 SUBMITTED.THEY MAY BE SUBMITTED WITH
 THE ROOF PERMIT APPLICATION, BUT
 SEPARATE FEES BASED ON VALUE WILL BE
 CHARGED.
  
 17.)THE ENERGY CALCS DIFFER IN SQUARE
 FOOTAGE, 20550 AND 19375.CLARIFY THE
 DISCREPANCY.
  
 18.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS, FBC13-103.1.
  
 19.)ADDITIONAL FEES DUE, SEE ATTACHED
 (RADON, FS404.056, FS166.021.
  
 WHEN RESUBMITTING, PROVIDE A RESPONSE
 LETTER STATING HOW EACH ITEM WAS
 ADDRESSED.