| 2006-05-12 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025.THIS APPEARS TO |
| | BE A CHANGE OF OCCUPANCY, FROM BUSINESS |
| | TO ASSEMBLY, FOR A PORTION OF THE |
| | BUILDING. |
| | |
| | LS1 SHOWS AN ADDITION OF 1000 SF.THIS |
| | SHOULD STATE WHETHER THIS IS HABITABLE |
| | SPACE OR NOT, AND IF IT IS, WHICH |
| | OCCUPANCY.IT APPEARS THAT THE ADDITION |
| | IS ROOF AREA ONLY, WHICH WILL NOT BE |
| | CALCULATED FOR IMPACT FEES BUT WHICH |
| | MUST BE INCLUDED FOR TABLE 503 |
| | COMPLIANCE. |
| | |
| | 3.)THE ACCESSIBLE PARKING DETAIL C7 IS |
| | TO COMPLY WITH CITY OF WEST PALM BEACH |
| | STANDARDS, SEE ATTACHED. |
| | |
| | 4.)THE DUMPSTER ENCLOSURES WILL |
| | REQUIRE A SEPARATE PERMIT.COMPLETE A |
| | PERMIT APPLICATION.SEPARATE PLANS ARE |
| | NOT REQUIRED. |
| | |
| | 5.)SEPARATE PERMIT REQUIRED FOR THE |
| | FENCES.SUBMIT SEPARATELY WITH PLANS. |
| | THIS ITEM DOES NOT NEED TO BE ADDRESSED |
| | PRIOR TO ISSUANCE OF THIS PERMIT, BUT |
| | MUST BE ADDRESSED PRIOR TO COMMENCEMENT |
| | OF THE FENCING WORK.INFORMATIONAL |
| | ONLY. |
| | |
| | 6.)SP1 REFERS TO MECHANICAL SHEET ???, |
| | PLEASE REVISE NOTE. |
| | |
| | 7.)AN EXISTING ACCESSIBLE ROUTE FROM |
| | THE PUBLIC WAY IS SHOWN.SHOW THE WIDTH |
| | AND MAX SLOPE, EITHER WITH A NOTE ON THE |
| | PLAN OR WITH EXISTING ELEVATIONS, TO |
| | SHOW COMPLIANCE WITH FBC11-4.1.2(1) AND |
| | (2), FBC11-4.1.6(1)(B). |
| | |
| | 8.)RAMP DETAIL 3-SP2 SHOWS 5FT AT THE |
| | BOTTOM OF THE RAMP.SEE FBC11-4.8.4(2), |
| | 72IN REQUIRED. |
| | |
| | 9.)WHAT IS THE "EXISTING CB" SHOWN ON |
| | THE NEW RAMP PLAN, 01-SP2?IT IS IN THE |
| | ACCESS AISLE FOR THE ACCESSIBLE PARKING |
| | SPACE.A SEARCH OF STANDARD |
| | ABBREVIATIONS WAS NOT HELPFUL.IF YOU |
| | USE NONSTANDARD ABBREVIATIONS, PLEASE |
| | INCLUDE A LEGEND. |
| | |
| | 10.)LS1, APPLICABLE CODES, 8-A2-3, AND |
| | OTHER DETAILS REFER TO ASCE7-98.THIS |
| | SHOULD BE ASCE7-02, FBC35. |
| | |
| | 11.)LS1 CODE SUMMARY REFERS TO TABLE |
| | 500.THIS IS TABLE 503 IN THE NEW CODE. |
| | |
| | 12.)LS1, PROVIDE CALCULATIONS FOR |
| | ALLOWABLE AREA INCREASES TO SHOW HOW YOU |
| | HAVE ARRIVED AT THE ALLOWABLE AREA. |
| | PLANS APPEAR CODE COMPLIANT BUT HOW YOU |
| | HAVE ARRIVED AT CODE COMPLIANCE SHOULD |
| | BE CLEAR.SEE ALSO FBC302.3.2. |
| | |
| | 13.)LS3, SOUTH STAIR, DOORS DO NOT |
| | LEAD TO AN EXIT; ONE DOOR OPENS INTO |
| | WHAT APPEARS TO BE A CLOSET, AND THE |
| | OTHER DOOR OPENS INTO THE FIRST FLOOR |
| | SPACE.TRAVEL DISTANCE FROM SECOND |
| | FLOOR FOR SECOND MEANS OF EGRESS IS NOT |
| | CLEAR. |
| | |
| | 14.)THE PLAN SHOWS ACCORDION SHUTTERS |
| | ON THE SECOND FLOOR.THIS MUST BE |
| | APPROVED BY THE BUILDING OFFICIAL, ITEM |
| | #14 OF THE MISSILE IMPACT PROTECTION |
| | STANDARD, ATTACHED.SUBMIT AN |
| | INSTALLATION PLAN AS REFERENCED IN ITEM |
| | #13. |
| | |
| | THE PLAN MAY BE SUBMITTED SEPARATELY |
| | FROM THE PERMIT APPLICATION RESUBMITTAL. |
| | FAILURE TO GET A PLAN APPROVED PRIOR TO |
| | RESUBMITTAL WILL RESULT IN DELAYS IN |
| | PERMIT ISSUANCE. |
| | |
| | THE INSTALLATION PLAN MAY BE SUBMITTED |
| | VIA EMAIL FOR PRELIMINARY REVIEW TO |
| | [email protected] PROVIDED ALL DOCUMENTATION |
| | IS LEGIBLE.A HARD COPY ORIGINAL SIGNED |
| | BY ALL PARTIES AFTER ALL COMMENTS HAVE |
| | BEEN ADDRESSED WILL BE REQUIRED FOR |
| | APPROVAL BY THE BUILDING OFFICIAL. |
| | |
| | 15.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DOR, FBC*106.3.3.SOME ARE |
| | REFERENCED SPECIFICALLY ON THE PLAN |
| | (SUCH AS ON A8-1), BUT OTHERS (SUCH AS |
| | THE ROOF PRODUCTS) ARE NOT.FOR |
| | PRODUCTS NOT REFERENCED BY NOA NUMBER ON |
| | THE PLAN, PLEASE REVIEW AND SHOW |
| | COMPLIANCE EITHER BY LETTER OR BY A |
| | REVIEW STAMP. |
| | |
| | 16.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED, FAC9B72.IF A |
| | FLORIDA STATE PRODUCT APPROVAL IS NOT |
| | AVAILABLE, AND YOU HAVE SUBMITTED A NOA, |
| | PLEASE ADVISE AND A LOCAL PRODUCT |
| | APPROVAL WILL BE ISSUED. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | STOREFRONT SYSTEM >10',NOA 01-0228.09 |
| | IS EXPIRED.ALSO THIS REQUIRES A |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL. |
| | THE NOA MUST BE CURRENT FOR A LOCAL TO |
| | BE ISSUED FROM THE NOA.A LOCAL PRODUCT |
| | APPROVAL CAN BE ISSUED WITH EITHER A |
| | TEST OR EVALUATION REPORT, PLEASE READ |
| | FAC9B72. |
| | |
| | STOREFRONT SYSTEM < 10', FLORIDA STATE |
| | PRODUCT APPROVAL 5844 WAS SUBMITTED. |
| | SUBMIT THE NOA REFERENCED ON THE STATE |
| | APPROVAL FOR VERIFICATION OF DESIGN |
| | PRESSURES AND FOR INSTALLATION |
| | INSTRUCTIONS IN THE FIELD.NOTE THE |
| | PRODUCT LIMITATION THAT PRESSURES ARE TO |
| | BE DIVIDED BY 1.33 OR VERIFIED BY A |
| | FLORIDA PE. |
| | |
| | CECO DOOR, A NOA WAS PROVIDED.A LOCAL |
| | PRODUCT APPROVAL HAS ALREADY BEEN ISSUED |
| | FOR THIS PRODUCT.PLEASE HAVE DOR |
| | REVIEW. |
| | |
| | ACCORDION SHUTTER, REQUIRES DOR REVIEW |
| | AND BACKUP AND NOA REFERENCED IN THE |
| | FLORIDA STATE PRODUCT APPROVAL.CIRCLE |
| | THE DETAILS WHICH APPLY TO THIS |
| | INSTALLATION.SHOW ANCHORING SPACING. |
| | THIS CAN BE DONE BY EITHER COMPLETING A |
| | SCHEDULE SUCH AS THE SAMPLE FORM |
| | ATTACHED OR BY CIRCLING IT ON THE |
| | PRODUCT APPROVAL. |
| | |
| | STOREFRONT DOOR, THE NOA PROVIDED AND |
| | REFERENCED ON A8-1 IS NON IMPACT.THE |
| | PLANS STATE IMPACT.ADDRESS.THE SHEET |
| | PROVIDED IS NOT A FLORIDA STATE PRODUCT |
| | APPROVAL, IT IS THE SEARCH RESULT. |
| | PROVIDE THE FLORIDA STATE PRODUCT |
| | APPROVAL.SEE THE OTHERS SUBMITTED AS |
| | THE OTHERS WERE PRINTED PROPERLY. |
| | |
| | LOUVER, PROVIDE FLORIDA STATE PRODUCT |
| | APPROVAL.IF ONE IS NOT AVAILABLE, A |
| | LOCAL WILL BE ISSUED USING THE NOA. |
| | |
| | NO PRODUCT APPROVALS FOR THE ROOF WERE |
| | SUBMITTED.THEY MAY BE SUBMITTED WITH |
| | THE ROOF PERMIT APPLICATION, BUT |
| | SEPARATE FEES BASED ON VALUE WILL BE |
| | CHARGED. |
| | |
| | 17.)THE ENERGY CALCS DIFFER IN SQUARE |
| | FOOTAGE, 20550 AND 19375.CLARIFY THE |
| | DISCREPANCY. |
| | |
| | 18.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS, FBC13-103.1. |
| | |
| | 19.)ADDITIONAL FEES DUE, SEE ATTACHED |
| | (RADON, FS404.056, FS166.021. |
| | |
| | WHEN RESUBMITTING, PROVIDE A RESPONSE |
| | LETTER STATING HOW EACH ITEM WAS |
| | ADDRESSED. |