| 2006-08-04 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: |
| | |
| | ***NOTE: |
| | CAPITAL LETTERS REFLECT ORIGINAL |
| | COMMENTS. LOWER CASE LETTERS REFLECT |
| | COMMENTS TO SUBMITTAL PACKAGE. |
| | |
| | 1- PROVIDE COMPLETE SET OF STRUCTURAL |
| | DRAWINGS SHOWING STRUCTURAL WORK TO BE |
| | PERFORMED WITH COMPLETE SPECIFICATIONS |
| | AND DETAILSTHAT COMPLY WITH SECTION |
| | 1609 OF FBC 2004 AND EXISTING BUILDINGS |
| | 2004 CODE. |
| | |
| | *** NO DONE. STRUCTURAL DRAWINGS WERE |
| | NOT SUBMITTED. THERE IS NOT INFORMATION |
| | GIVEN FOR REPLACING FRAMING AND SIDING. |
| | |
| | *** PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR STRUCTURAL FRAMING |
| | CONNECTORS THAT WILL BE SPECIFIED ON THE STRUCTURAL |
| | DRAWINGS. |
| | |
| | *** PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR SIDING TO BE INSTALLED AS |
| | REQUIRED BY RULE 9B-72 OF DCA. |
| | |
| | *** ENGINEER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITTING ALL PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE AS REQUIRED BY SEC. 106.3.3 OF |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | *** WHAT IS THE INTENTION OF THE LETTER |
| | FROM ENGINEERING EXPRESS?. IF IT IS TO |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| | DOUBLE HUNG WINDOW, THEN, IT'S |
| | INCOMPLETE. NEED TO PROVIDE THE COMPLETE |
| | PACKAGE INCLUDING THE LOCAL PRODUCT |
| | APPROVAL APPLICATION AND QUALITY |
| | ASSURANCE (ENGINEER'S LETTER CERTIFYING |
| | THAT PRODUCT WAS CONSTRUED AND INSTALLED |
| | AS PER DESIGN SPECFIFICATIONS |
| | SUBMITTED). THEN, IT WILL BE |
| | FORWARDED TO ROBERT BROWN FOR LOCAL |
| | PRODUCT APPROVAL REVIEW.CALL ROBERT |
| | BROWN AT (561)805-6652 FOR QUESTIONS |
| | REGARDING LOCAL PRODUCT APPROVAL REVIEW |
| | TIME AND QUALITY ASSURANCE REQUIRED FOR |
| | ONE OF A KIND (SITE SPECIFIC) PRODUCT |
| | APPROVALS. |
| | |
| | 2- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| | PRODUCT APPROVALS FOR ALL TYPE AND SIZE |
| | OF WINDOWS AND WINDOWS TO BE REPLACED AS |
| | REQUIRED BY RULE 9B-72 OF DEPARTMENT OF |
| | COMMUNITY AFFAIRS (DCA). GO TO THE |
| | WEBSITE WWW.FLORIDABUILDING.ORG TO FIND |
| | ALL INFORMATION REGARDING PRODUCT |
| | APPROVALS IN FLORIDA. |
| | INFORMATION SUBMITTED IS NOT ACCEPTABLE. |
| | NEED COMPLETE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL PACKAGE. |
| | |
| | *** WINDOW AND DOOR APPLICATIONS |
| | SUBMITTED FOR LOCAL PRODUCT APPROVAL |
| | WILL BE FORWARDED TO ROBERT BROWN, PLAN |
| | REVIEWER'S MANAGER, FOR LOCAL PRODUCT |
| | APPROVAL REVIEW. CALL ROBERT BROWN FOR |
| | QUESTIONS REGARDING PRODUCT APPROVAL |
| | REVIEW TIMING AND QUALITY ASSURANCE FOR |
| | ONE OF A KIND (SITE SPECIFIC) PRODUCT |
| | APPROVALS. |
| | |
| | *** DOOR STYLE SUBMITTED FOR LOCAL |
| | PRODUCT APPROVAL DOESN'T MATCH DRAWINGS |
| | SHOWN IN BLUEPRINT. |
| | |
| | *** PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR DOUBLE HUNG WINDOW. |
| | |
| | *** PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR STORM SHUTTERS> GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| | FLORIDA PRODUCT APPROVALS. |
| | |
| | *** PROVIDE KEY PLAN AND A COMPLETE |
| | INSTALLATION SCHEDULE FOR STORM |
| | SHUTTERS. SEE ATTACHED SAMPLE OF STORM |
| | SHUTTERS INSTALLATION SCHEDULE. |
| | |
| | 3- PROVIDE STRUCTURAL BUCK DETAILS FOR |
| | DOORS AND WINDOWS AS REQUIRED BY SEC. |
| | 1714.5.4.2 FBC 2004. |
| | |
| | ***NO DONE. |
| | |
| | 4- PROVIDE 2 SETS OF SIGNED AND SEALED |
| | PLANS AND 2 SETS OF FLORIDA OR LOCAL |
| | PRODUCT APPROVALS FOR EACH TYPE OF DOOR |
| | AND WINDOW. |
| | |
| | *** NEED 2 LOCAL PRODUCT APPROVAL |
| | APPLICATIONS PER DOOR OR WINDOW. ONLY |
| | ONE SUBMITTED. |
| | |
| | 5- NOTICE OF COMMENCEMENT DOESN'T HAVE |
| | ANY DESCRIPTION FOR THE GENERAL |
| | DESCRIPTION OF IMPROVEMENTS. COMPLETE |
| | INFORMATION AND RE-RECORD THE NOTICE OF COMMENCEMENT. |
| | |
| | *** NO DONE. |
| | |
| | 6- VALUATION OF PROJECT WILL BE |
| | EVALUATED AFTER COMPLETE SET OF DRAWINGS |
| | ARE SUBMITTED TO DEFINE SPECIFIC SCOPE |
| | OF WORK. |
| | |
| | *** NO DONE. UNABLE TO DETERMINE SCOPE |
| | OF WORK. NO PLANS SUBMITTED SHOWING |
| | EXTEND OF WORK. |
| | |
| | |