| 2006-07-02 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| | |
| | ** PLEASE SEE SOME NOTS FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE: OK,NO, PLEASE SEE NEW |
| | ELECTRICAL SHEETS ARE OK, HOWEVER NEW |
| | SHEET "C-1" CONTAINS A RAISED SEAL OVER |
| | A COLORED PHOTO-COPY OF SIGNATURE WHICH |
| | IS REQUIRED TO BE ORIGINAL UNDER FS |
| | 471.025. |
| | PLEASE KNOW, COPIES OF THESE SHEETS ARE |
| | BEING RETAINED AND WILL PLACED WITH |
| | OTHER PREVIOUS PLANS WHICH WERE ALSO |
| | SEALED PHOTO-COPIES OF THE DESIGNER'S |
| | SIGNATURE. |
| | PLEASE KNOW, PLANS NOW MAY BE TURNED |
| | OVER TO THE FLORIDA BOARD OF ENGINEERS |
| | AND STATE'S LEGAL COUNSEL TO THE FBPE'S |
| | FOR REVIEW OF SAID PLANS. |
| | ** PLEASE KNOW, THIS HAS BEEN |
| | PREVIOUSLY NOTED ON THIS PERMIT AND MANY |
| | OTHER PROJECTS WHICH ARE BEING DONE BY |
| | THIS FIRM AND ALL PLANS FROM ALL |
| | PROJECTS HAVE BEEN RETAINED AS THIS |
| | COMMENT IS BEING REPEATED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS ARE CONTAIN A |
| | RAISED SEALED ON PLANS WHICH ARE |
| | PHOTO-COPIES OF THE SIGNATURE FOR THE |
| | ENGINEER OF RECORD. |
| | PLEASE KNOW, BOTH SETS OF PLANS ARE |
| | BEING RETAINED. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.002, |
| | WHICH REQUIRES BOTH SETS TO CONTAIN AN |
| | ORIGINAL SIGNATURE. |
| | |
| | 2) NOTE: NO, THIS HAS NOT BEEN ADJUSTED |
| | AND A VALUE WILL BE ACCESSED BY THIS |
| | OFFICE BEFORE PERMIT ISSUANCE USING THE |
| | "MARSHALLS/ SWIFT" GUIDE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC ADMINISTRATIVE |
| | SECTION 108.3 WHICH VALUE FOR COMPLETE |
| | SCOPE OF WORK SHALL INCLUDE ALL LABOUR |
| | AND MATERIALS WHETHER OR NOT ANY |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | PLEASE SEE VALUE OF $5K IS NOT ACCURATE |
| | FIGURE.PLEASE ADJUST. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: NO, PLEASE SEE PANEL "PPC" DOES |
| | NOT INDICATE IF IT CONTAINS A MCB. |
| | PLEASE KNOW, IF THIS PANEL DOES NOT |
| | CONTAIN A MCB, A DISCONNECT RATED FOR |
| | THE LOAD SERVED SHALL BE GROUPED WITH |
| | OTHER MAIN IN ORDER TO SHUT OFF POWER |
| | FOR FEEDERS COMING TO THIS EQUIPMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE IF PANEL SHOWN |
| | CONTAINS A MCB AND IF THIS IS RGOUPED |
| | WITH ANY OTHER MAINS. RISER SHOWS "TO |
| | EXISTING POWER SOURCE" HOWEVER THIS |
| | SOURCE IS NOT CLEAR? METER, MAIN ? |
| | PLEASE KNOW, THE DISCONNECTING MEANS |
| | SHALL ALL MEET |
| | 230.70,230.72,225.31-225.39, |
| | 230.76,230.79. |
| | |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |