Plan Review Notes
Plan Review Notes For Permit 06031314
Permit Number 06031314
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-02 00:00:00*********** UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOME NOTS FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE: OK,NO, PLEASE SEE NEW
 ELECTRICAL SHEETS ARE OK, HOWEVER NEW
 SHEET "C-1" CONTAINS A RAISED SEAL OVER
 A COLORED PHOTO-COPY OF SIGNATURE WHICH
 IS REQUIRED TO BE ORIGINAL UNDER FS
 471.025.
 PLEASE KNOW, COPIES OF THESE SHEETS ARE
 BEING RETAINED AND WILL PLACED WITH
 OTHER PREVIOUS PLANS WHICH WERE ALSO
 SEALED PHOTO-COPIES OF THE DESIGNER'S
 SIGNATURE.
 PLEASE KNOW, PLANS NOW MAY BE TURNED
 OVER TO THE FLORIDA BOARD OF ENGINEERS
 AND STATE'S LEGAL COUNSEL TO THE FBPE'S
 FOR REVIEW OF SAID PLANS.
 ** PLEASE KNOW, THIS HAS BEEN
 PREVIOUSLY NOTED ON THIS PERMIT AND MANY
 OTHER PROJECTS WHICH ARE BEING DONE BY
 THIS FIRM AND ALL PLANS FROM ALL
 PROJECTS HAVE BEEN RETAINED AS THIS
 COMMENT IS BEING REPEATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE CONTAIN A
 RAISED SEALED ON PLANS WHICH ARE
 PHOTO-COPIES OF THE SIGNATURE FOR THE
 ENGINEER OF RECORD.
 PLEASE KNOW, BOTH SETS OF PLANS ARE
 BEING RETAINED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002,
 WHICH REQUIRES BOTH SETS TO CONTAIN AN
 ORIGINAL SIGNATURE.
  
 2) NOTE: NO, THIS HAS NOT BEEN ADJUSTED
 AND A VALUE WILL BE ACCESSED BY THIS
 OFFICE BEFORE PERMIT ISSUANCE USING THE
 "MARSHALLS/ SWIFT" GUIDE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOUR
 AND MATERIALS WHETHER OR NOT ANY
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE VALUE OF $5K IS NOT ACCURATE
 FIGURE.PLEASE ADJUST.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE SEE PANEL "PPC" DOES
 NOT INDICATE IF IT CONTAINS A MCB.
 PLEASE KNOW, IF THIS PANEL DOES NOT
 CONTAIN A MCB, A DISCONNECT RATED FOR
 THE LOAD SERVED SHALL BE GROUPED WITH
 OTHER MAIN IN ORDER TO SHUT OFF POWER
 FOR FEEDERS COMING TO THIS EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE IF PANEL SHOWN
 CONTAINS A MCB AND IF THIS IS RGOUPED
 WITH ANY OTHER MAINS. RISER SHOWS "TO
 EXISTING POWER SOURCE" HOWEVER THIS
 SOURCE IS NOT CLEAR? METER, MAIN ?
 PLEASE KNOW, THE DISCONNECTING MEANS
 SHALL ALL MEET
 230.70,230.72,225.31-225.39,
 230.76,230.79.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  