2006-05-10 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTES
 #1,2, AND 5.
  
 2) PLEASE BE ADVISED AND NOTE ON PLANS.
 GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.