2006-04-26 00:00:00************* UNSAT *************
  
 1) NOTE: PLEASE SEE PLANS ARE CONTAIN A
 RAISED SEALED ON PLANS WHICH ARE
 PHOTO-COPIES OF THE SIGNATURE FOR THE
 ENGINEER OF RECORD.
 PLEASE KNOW, BOTH SETS OF PLANS ARE
 BEING RETAINED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002,
 WHICH REQUIRES BOTH SETS TO CONTAIN AN
 ORIGINAL SIGNATURE.
  
 2) NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOUR
 AND MATERIALS WHETHER OR NOT ANY
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE VALUE OF $5K IS NOT ACCURATE
 FIGURE.PLEASE ADJUST.
  
 3) NOTE: PLEASE PROVIDE IDENTIFICATION
 ON SITE PLANS E-2 OF ALL EQUIPMENT.
 (PANEL, ATS ETC.)
 PLEASE SEE CONDUITS FROM GEN APPEAR TO
 BE SHOWN HEADING TOWARD FENCE LINE, AND
 PLANS ONLY INDICATES METER BOARD?
 215.5
  
 4) NOTE: PLEASE CORRELATE THE ATS BEING
 INSTALLED. PLEASE SEE PLANS INDICATE
 ASCO AND SPECS SUBMITTED ARE SHOWING
 KOHLER.
 215.5
  
 5) NOTE: PLEASE INDICATE THE FLOOD ZONE
 ON SITE PLAN, (IF ANY) AND ELEVATION OF
 EQUIPMENT.
  
 6) NOTE: PLEASE INDICATE OF PANEL SHOWN
 CONTAINS A MCB AND IF THIS IS RGOUPED
 WITH ANY OTHER MAINS. RISER SHOWS "TO
 EXISTING POWER SOURCE" HOWEVER THIS
 SOURCE IS NOT CLEAR? METER, MAIN ?
 PLEASE KNOW, THE DISCONNECTING MEANS
 SHALL ALL MEET
 230.70,230.72,225.31-225.39,
 230.76,230.79.
  
  
 ** PLEASE KNOW, THE SITE PLAN CONTAINING
 THE ZONING SIGN OFF HAS BEEN VOIDED DUE
 TO THE FACT THE PLANS ARE SEALED
 PHOTO-COPIES.
 ZONING WILL BE REQUIRED TO RE-STAMPED
 NEW PLANS WHEN PACKAGE IS RESUBMITTED
 ONCE ALL REVIEWS ARE COMPLETED.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]