| Plan Review Notes For Permit 06031303 |
| Permit Number |
06031303 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-31 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | | 20,900 TOTAL BTU'S AND THE MECHANICAL | | | PLANS ARE CALLING FOR 29,800 TOTAL | | | BTU'S, THE PLANS CAN NOT CALL FOR MORE | | | BTU'S THAN THE ENERGY CAL'S. PLEASE | | | CORRECT. | | | | | | 2) PLEASE SUBMIT MANUAL J CALCULATIONS, | | | PER 2004 FBC/R M1401.3 . | | | | | | 3) CLOTHES DRYER VENT MUST DISCHARGE A | | | MIN. OF 4 FEET FROM THE A/C CONDENSER | | | UNIT, PER 2004 FBC/M 501.2 . PLEASE | | | CORRECT. | | | | | | 4) THE BATHROOM EXHAUST FAN CAN NOT | | | DISCHARGE OVER A WINDOW, PER 2004 FBC/M | | | 501.2 . PLEASE CORRECT. | | | | | | 5) ELECTRICAL PLANS ARE CALLING FOR A 10 | | | KW HEATER AND THE MECHANICAL PLANS ARE | | | CALLING FOR A 8 KW HEATER, THE TWO MUST | | | COINSIDE PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|