Plan Review Notes
Plan Review Notes For Permit 06031303
Permit Number 06031303
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-31 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTES MENTIONS WORK
 PER "PALM BEACH COUNTY", PLEASE SEE
 SCOPE OF WORK IS LOCATED IN THE CITY OF
 WEST PALM BEACH.
 PLEASE ADJUST
 PLEASE ALSO KNOW, ONCE ALL REVIEW BY
 ADDRESSING DEPARTMENT IS DONE, AN
 ADDRESS FOR THIS PROJECT WILL BE ISSUED.
 PLEASE ADJUST TITLE BLOCKS TO INCLUDE
 THE NEW ADDRESS. FAC 61G1-16.004
  
 2) NOTE: PLEASE CORRELATE A/C HEAT
 LOADS. MECH PLANS INDICATE 8KW,
 ELECTRICAL PLANS INDICATE 10 KW?
 PLEASE ADJUST AS NEEDED.
 ** PLEASE ALSO SEE LOAD CALCULATIONS AS
 THE LOADS ARE SHOWN AS THE HIGHER LOAD
 WHICH IS THE AHU (10KW), HOWEVER THE
 IDENTIFICATION IS NOTED AS THE A/C
 COMP.?
 PLEASE ADJUST. THIS HAS BEEN REDLINED ON
 OTHER PLANS AND SEEMS TO BE A MISPRINT
 IN PLANS.
  
 3) NOTE: PLEASE SEE BATH CIRCUIT(S) ARE
 REQUIRED TO BE 20A, #12,
 210.52D,210.11C3
 (SHOWN AS 15A #14)
  
 4) NOTE: PLEASE SHOW DISCONNECT FOR AHU.
 440.11
  
 5) NOTE: PLEASE SEE RISER SHOWS A MAIN
 DISCONNECT OUTSIDE , HOWEVER PLANS ONLY
 SHOW THE 200A METER.
  
 PLANS ARE GENERALLY IN GOOD SHAPE,
 HOWEVER THEY ARE COMING BACK FOR OTHER
 COMMENTS AND THE ABOVE SHOULD BE
 CORRECTED AT THIS TIME.
  
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** WHEN AND BEFORE RESUBMITTING PLANS,
 PLEASE COMPLETELY REMOVED ANY OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ON ECOPY OF THE REMOVED OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE AN QUESTIONS,
 PLEASE DO NOT HESITE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]