Plan Review Notes
Plan Review Notes For Permit 06031299
Permit Number 06031299
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 MYRON JACOBS(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1609 THE SYSTEM SELECTED FROM THE
 SUBMITTED FLAT ROOF PRODUCT APPROVAL NOA
 HAS A MAXIMUM DESIGN PRESSURE OF LESS
 THAN -89 PSF AND CITES GENERAL
 LIMITATION #9. GENERAL LIMITATION #9
 PROHIBITS RATIONAL ANALYSIS OR
 EXTRAPOLATION TO ENHANCE THE UPLIFT
 PRESSURE AT PERIMETER AND CORNER AREAS
 BY REDUCING THE FASTENER SPACING IN
 THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS). ALSO IF GENERAL
 LIMITATION #7 IS USED, CALCULATIONS
 SIGNED AND SEALED SHALL BE DONE BY A
 FLORIDA REGISTERED PROFESSIONAL
 ENGINEER,ARCHITECT OR ROOF
 CONSULTANT.SEE PG 22.
 PLEASE HI-LIGHT OR CIRCLE WHICH APPROVED
 ASSEMBLY WILL BE USED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  