| 2006-05-18 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- ACCORDING TO THE DIMENSIONS GIVEN BY |
| | THE ENGINEER(L:25' AND W:24') TOTAL AREA |
| | IS 600SF. BUT PERMIT APPLICATION SAYS |
| | 900SF. INFORMATION NEED TO MATCH. REVISE |
| | AS REQUIRED. |
| | |
| | 2- ENGINEER TO CAREFULLY REVIEW SPECIFIC |
| | PRODUCT APPROVAL TO CORRECT THE |
| | FOLLOWING: |
| | A) CLEARLY IDENTIFY SPECIFIC ASSEMBLY |
| | FROM THE APPROVED ASSEMBLIES LISTED IN |
| | THE PRODUCT APPROVAL FOR WHICH THESE |
| | CALCULATIONS ARE DONE FOR. |
| | B) FASTENER TYPE DOESN'T MATCH |
| | FASTENER TYPE SHOWN ON THE PRODUCT |
| | APPROVAL. |
| | C) FASTENER SPACING AT SIDE LAP (8") |
| | FOR ZONE ONE DOESN'T MATCH FASTENER |
| | SPACING SHOWN ON PRODUCT APPROVAL (12"). |
| | D) NOA NUMBER SPECIFIED ON FIRST SHEET |
| | DOESN'T MATCH NOA NUMBER SPECIFIED ON |
| | SHEET ONE OF CALCULATIONS. THERE ARE |
| | SIGNIFICANT DIFFERENCES BETWEEN THOSE |
| | TWO NOA'S. |
| | E) BASE SHEET WIDTH DIMENSION IS |
| | INCORRECT. SEE PRODUCT APPROVAL FOR |
| | CORRECT DIMENSION. |
| | F) DESIGN PRESSURES ON SHEET ONE OF |
| | CALCULATIONS DON'T MATCH THE DESIGN |
| | PRESSURES SHOWN ON NOA 03-0130.08. |
| | NOTE: ALSO, SEE CORRECT NOA NUMBER. LAST |
| | TWO DIGITS AFTER THE PERIOD ARE .O8, NOT |
| | .8. |
| | G) FASTENER SHOWN ON THE CALCULATION |
| | SHEET ONE DOESN'T MATCH FASTENER SHOWN |
| | ON FIRST PAGE OF ENGINEER'S REPORT. |
| | H) REVISE INFORMATION ON FASTENER |
| | DIAGRAM SHEET: FASTENER SPACING AT SIDE |
| | LAP FOR ZONE ONE AND CORRECT WIDTH |
| | DIMENSION FOR BASE SHEET. |
| | I) ENGINEER TO SIGN, SEAL AND DATE ALL |
| | FOUR PAGES AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE AND FAC 61G15-23.002. |
| | |
| | NOTE: |
| | ONE SET OF THE SUBMITTED PACKAGE WAS |
| | RETAINED IN THIS OFFICE TO SUBMIT TO THE |
| | BOARD OF PROFESSIONAL ENGINEERS FOR |
| | THEIR REVIEW. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |