| 2006-05-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)SHEET A.0 DECLARES BUILDING TYPE AS |
| | 1V.SEE FBC6, THIS SHOULD REFER TO A OR |
| | B. |
| | |
| | 3.)DECLARE BUILDING SIZE, FBC5. |
| | |
| | 4.)OCCUPANCY IS TO BE ONE IN CHAPTER |
| | 3."PUMP HOUSE" IS NOT AN OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 5.)PROVIDE FLOOD ZONE DESIGNATION.IF |
| | THIS IS LOCATED IN A HIGH HAZARD FLOOD |
| | ZONE, THE FINISHED FLOOR IS TO BE 6" |
| | ABOVE BFE, CITY OF WEST PALM BEACH |
| | MUNICIPAL CODE 94-546(B).IF THIS IS IN |
| | A HIGH HAZARD FLOOD ZONE, DECLARE BFE |
| | AND SHOW MINIMUM FFE ON THE PLAN.FORM |
| | BOARD WITH ELEVATIONS WILL BE REQUIRED. |
| | |
| | 6.)ALL PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD |
| | FBC*106.3.3. |
| | |
| | 7.)PROVIDE INSTALLATION INSTRUCTIONS |
| | FROM THE MANUFACTUER FOR THE SKYLIGHT. |
| | |
| | 8.)THE FLORIDA STATE PRODUCT APPROVALS |
| | FOR THE CONNECTORS ARE EXPIRED, 2001 |
| | CODE RATHER THAN 2004. |
| | |
| | 9.)PROVIDE WIND DESIGN INFORMATION |
| | REQUIRED BY FBC1603.1.4. |
| | |
| | 10.)SHUTTERS ARE REQUIRED FOR THE |
| | LOUVERED DOOR.SHUTTERS FOR COMMERCIAL |
| | BUILDINGS MUST BE APPROVED BY THE |
| | BUILDING OFFICIAL.SEE ATTACHED POLICY, |
| | ITEM 13.SUBMIT AN INSTALLATION PLAN. |
| | FAILURE TO ADDRESS THIS COMMENT WILL |
| | RESULT IN DELAYS IN PERMITTING.THE |
| | PLAN MAY BE SUBMITTED SEPARATELY FROM |
| | THE PERMIT RESUBMITTAL. |
| | |
| | 11.)PROVIDE THE APPROVED ASSEMBLY YOU |
| | ARE USING FOR THE FLAT DECK. |
| | |
| | 12.)THE SPEC SHEET FOR THE ROOF IS FOR |
| | A CONCRETE DECK, THIS IS WOOD. |
| | |
| | 13.)THE SITE PLAN IS REQUIRED TO SHOW |
| | TABLE 601 COMPLIANCE.PROVIDE A SIGNED, |
| | SEALED, DATED SITE PLAN SHOWING DISTANCE |
| | TO EITHER THE PROPERTY LINE OR TO |
| | ADJACENT BUILDINGS AND ASSUMED PROPERTY |
| | LINES. |
| | |
| | 14.)DOCUMENTS PREPARED BY A LANDSCAPE |
| | ARCHITECT ARE TO BE SIGNED, SEALED, |
| | DATED ORIGINALS FS481.306.THE SITE |
| | PLAN PREPARED BY URBAN DESIGN DOES NOT |
| | SHOW THE PROPOSED IMPROVEMENT.SEE ALSO |
| | #13. |
| | |
| | |