| 2006-05-15 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE CONSTRUCTION TYPE AND |
| | TYPE OF OCCUPANCY BASED ON THE 2004 |
| | FLORIDA BUILDING CODE. SEE #3 FROM |
| | PERVIOUS COMMENTS. |
| | |
| | 2)THE WINDLOAD DATA ON THE PLAN |
| | REFRENCES FBC 1606.1.7. THIS SECTION HAS |
| | CHANGED IN THE 2004 FBC TO 1603.1.4. |
| | PLEASE CORRECT. |
| | |
| | 3) SPECIFY THE FASTENING REQUIREMENTS |
| | FOR THE 3/4" PLYWOOD ROOF SHEATHING AS |
| | REQUIRED BY 2004 FBC TABLE 2304.9.1. |
| | #31, WHICH REQUIRES FASTENER SPACING OF |
| | 4" OC AT COMPONENT AND CLADDING ROOF |
| | ZONE 3. SEE COMMENT #8 FROM PREVIOUS |
| | REVIEW. |
| | |
| | 4) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE ROOFING MATERIAL DOES NOT MEET THE |
| | REQUIRED UPLIFT PRESSURE. PRODUCT |
| | APPROVAL LISTS MAXIMUM DESIGN PRESSURE |
| | AS -45 PSF WITH NO ENHANCED FASTENING |
| | ALLOWED. THE REQUIRED PRESSURES FROM |
| | TABLE 1609.6B ARE -59.2 AT PERMITER |
| | AREAS AND -89.0 AT THE CORNERS. SUBMIT |
| | APPROPRIATE PRODUCT APPROVAL. |
| | |
| | 5) THE FIGURES GIVEN IN THE COMPONENT |
| | AND CLADDING TABLE ON THE PLANS ARE FOR |
| | A STRUCTURE WITH A ROOF SLOPE GREATER |
| | THAN 10 DEGREES. THESE STRUCTURES HAVE |
| | SLOPES LESS THAN 10 DEGREES. PLEASE |
| | CORRECT. SEE FBC TABLE 1609.6B. |
| | |
| | 6) THE PLANS REFERENCE ASCE 7-98. THE |
| | AMENDMENTS TO THE 2004 FBC CHANGED THE |
| | EDITION OF ASCE 7 TO ASCE 7-02. |
| | |
| | 7) INDICATE HOW THE ACCESSIBLE ROUTE |
| | WILL BE MAINTAINED INTO OFFICE 1 FROM |
| | THE EXTERIOR AND OFFICE 2 FROM BOTH THE |
| | EXTERIOR AND INTERIOR AFTER THE SLABS |
| | ARE RAISED (FBC 11-4.1.6). SEE COMMENT |
| | #12 FROM PREVIOUS REVIEW. SPECIFY THE |
| | ELEVATION CHANGES AND PROVIDE DETAILS OF |
| | RAMPS, ETC. |
| | |
| | 8) SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR EXTERIOR DOORS THAT HAVE |
| | BEEN APPROVED BY THE DESIGNER OF RECORD |
| | PER FBC 106.3.3 AS AMENDED BY CITY OF |
| | WPB. |
| | |
| | 9) TWO COPIES OF ALL PRODUCT APPROVALS |
| | ARE REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |