| Date |
Text |
| 2006-07-16 00:00:00 | |
| | **** UNSAT 2ND REVIEW ***** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE: OK/NO, PLEASE SEE THIS WAS DONW |
| | ON ELECTRICAL PLANS HOWEVER PLEASE SEE |
| | COVER SHEETS STILL REFLECT THE 1999 |
| | LS101. |
| | PLEASE SEE THIS SHOULE BE THE 2003. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE BE SURE PLANS REFLECT |
| | THE FOLLOWING CODES. |
| | NFPA-101 2003, NFPA-70 2002, NFPA-72 |
| | 2002. PLEASE KNOW, THIS IS FOR |
| | ELECTRICAL AND ARCHITECTURAL SHEETS. |
| | |
| | 2) NOTE: NO, PLEASE SEE TITLE BLOCKS ARE |
| | STILL MISSING THE REQUIRED CERTIFICATE |
| | OF AUTHORIZATION NUMBER FOR ALL SHEETS |
| | CONTAINING "INTERIOR ARCHITECTS. |
| | PLEASE SEE NUMEROUS PRINT OUT FROM THE |
| | STATE OF FLORIDA WEBSITEDBPR WHICH |
| | INDICATES THE ARCHITECT OF RECORD MR |
| | ANGELO LUIS LEBRON BEING THE QUALIFYING |
| | ARCHITECT AND RESPONSIBLE SUPERVISOR FOR |
| | A "INTERIOR ARCHITECTS PC" LOCATED IN |
| | SAN FRANCISCO CA. |
| | PLEASE SEE THERE A CA NUMBER FOR THAT |
| | COMPANY SHOWN ON THE STATE'S SITE. |
| | ** IMPORTANT** PLEASE SEE ALL LOCATIONS |
| | ON PLANS AND TITLE BLOCK INDICATE THE |
| | ARCHITECT'S LICENSE NUMBER AS 18990, |
| | WHEN THE SEAL INDICATES #16990 AND THE |
| | STATE'S WEBSITE ALSO LIST #16990. THIS |
| | SEEMS TO BE A MISPRINT OF THE WRONG |
| | NUMBER. ?? PLEASE SEE THAT A CERTIFICATE |
| | OF AUTHORIZATION NUMBER IS OBTAINED FOR |
| | COMPANY AS LISTED ON TITLE BLOCKS AND |
| | PLEASE BE SURE TO PLACE THIS NUMBER ON |
| | PLANS AS REQUIRED UNDER FAC 61G1-16.004, |
| | FS 481.219 |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS FOR THE ARCHITECT, |
| | ARCHITECTURAL FIRM. |
| | PLEASE SEE MISSING THE PRINTED NAME, |
| | PRINTED LINCENSE # FOR SIAD ARCHITECT. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION #. |
| | PLEASE SEE ABOVE ALL REQUIRED UNDER THE |
| | FLORIDA ADMINISTIVE CODE 61G1-16.004 AND |
| | FLORIDA STATUES, 481.219 |
| | ** PLEASE KNOW THIS INFORMATION IS |
| | REQUIRED ON ALL SHEETS AND FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OF THE OTHER REVIEWERS. |
| | |
| | 3) NOTE:OK, ENGINEERING FIRM'S TITLE |
| | BLOCK WAS CORRECTED. |
| | |
| | 4 )NOTE: OK. |
| | |
| | 5) NOTE: NO, PLEASE SEE LIGHTING |
| | CALCULATIONS FOR LIGHTING POWER |
| | DENSITIES,WATTAGE PERMITTED AND ACTUAL |
| | WATTAGE PERMITTED COULD NOT BE LOCATED. |
| | THIS COULD NOT BE LOCATED ON PLANS OR |
| | ENERGY CALCS. |
| | PLEASE SEE 13-415.1.ABC.1, TABLES |
| | 415.2.C.1, 415.2.B1. |
| | IF THIS CAN BE NOTED ON PLANS, THIS |
| | WOULD BE ACCEPTABLE. |
| | PLEASE ALSO SEE CONFERENCE ROOM IS NOTED |
| | AND SHOWN BEING CONTROLLED BY THE TIME |
| | CLOCK AND OVER RIDE DEVICE AT FRONT DOOR |
| | LOCATION, HOWEVER THIS SEEMS TO BE A |
| | "SEPARATE SPACE" WITH FLR TO CEILING |
| | HEIGHT PARTITIONS, WHICH WOULD ALSO |
| | REQUIRESEPARATE OVER-RIDE DEVICE(S). |
| | PLEASE SEE 13-415.1.ABC.1.3 |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1, .2 AND .3 ETC |
| | PLEASE SEE THE SYSTEM FOR ENERGY |
| | CONSERVATION SHALL BE BASED FOR ENTIRE |
| | AREA AND THE "OC" AS SHOWN MUST BE |
| | CAPABLE OF OVER-RIDING THE BASE SYSTEM. |
| | PLEASE PROVIDE INFORMATION ON TYOE OF OC |
| | BEING INSTALLED. |
| | PLEASE SEE SOME AREAS DO NOT INDICATE |
| | ALL CIRCUITING AS SHOWN AS PART OF THIS |
| | SYSTEM. |
| | PLEASE PROVIDE THE SCHEDULE FOR THESE |
| | FOR ALL AREAS. |
| | IT WAS NOTED THAT THE TIMED SPRING WOUND |
| | TIMER IS BEING INSTALLED IN SOME AREAS. |
| | PLEASE KNOW, COMMON AREA SHALL PROVIDE |
| | SOME SORT OF NOTICE FOR "LTS OUT" AND/OR |
| | EGRESS LTS PROVIDED. |
| | PLEASE PROVIDE DETAIL FOR THE |
| | OVER-RIDING OF THE TIME CLOCK SYSTEM AS |
| | NOTED ON PLANS. |
| | PLEASE SEE ABOVE REFERENCED CODES AS A |
| | OVERIDE DEVICE OF ONE OR MORE DEPENDING |
| | ON EGRESSED AREAS SHALL BE IN A READILY |
| | ACCESSIBLE LOCATION/ENTRANCE TO SPACE. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE:NO, PLEASE KNOW, IF THE RM IS |
| | NOT GOING TO RATED AND THE ELECTRICAL |
| | AND A/C SYSTEM SHOWN IS NOT GOING TO BE |
| | SHUT DOWN, THEN THE FOLLOWING MUST TAKE |
| | PLACE. |
| | THE RESPONSE MENTIONS THE RISK FACTORS |
| | WERE REVIEWED BY THE "CLIENT" AND BY |
| | THEIR DETERMINATION THIS ROOM DOES NOT |
| | REQUIRE RATING ETC. |
| | PLEASE OBTAIN ORIGINAL LETTER WHICH MUST |
| | BE ON COMPANY LETTER HEAD WHICH STATES |
| | THE ADDRESS LOCATION OF CONSIDERATION, |
| | THE RISK FACTORS, AND THAT THESE HAVE |
| | BEEN CONSIDERED, AND THAT THERE WOULD NO |
| | AFFECTS AS LISTED IN NFPA-75. |
| | *OR WORDS TO THAT AFFECT* |
| | PLEASE KNOW, THIS LETTER MUST SIGNED BY |
| | THE OWNER/CLIENT OF RECORD AND SHALL BE |
| | PROPERLY NOTORIZED UNDER FS 117.05. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLAN NOTES MENTIONS, |
| | INSTALLATION FOR ROOMS CONTAINING |
| | COMPUTER EQUIPMENT TO MEET 645. |
| | PLEASE SEE "LAN RM", PLEASE PROVIDE |
| | DETAILED INFORMATION ON THIS ROOM AS IT |
| | SEEMS TO IMPLEMENT THE CRITERIA FOR AN |
| | "IT" ROOM. NFPA-75 |
| | PLEASE PROVIDE DETAILS FOR ANY AREA |
| | BEING CONSIDERED AS AN "IT" FOR |
| | DISCONNECTING MEANS, FIRE RATINGS FOR |
| | RM, A/C SHUT DOWN ETC. |
| | |
| | ** WHEN RESUBMITTING PLANS, PLEASE |
| | SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS |
| | FOR REFERENCE ONLY.. |
| | |
| | PLEASE BE AWARE OF ANY POSSIBLE COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | EELCTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITE IN CONTACTING THIS |
| | OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected]. |