| Date |
Text |
| 2006-05-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS: DATE |
| | REQUIRED ON THE SEAL WHEN THE SEAL AND |
| | SIGNATURE ARE AFFIXED TO THE DOCUMENTS. |
| | THE TITLE BLOCK MUST, AT A MINIMUM, |
| | CONTAIN AMONG OTHER REQUIREMENTS, (2) |
| | FIRM LICENSE NUMBER, (5) A SPACE FOR THE |
| | SIGNATURE & DATED SEAL, & (6) A SPACE |
| | FOR THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT. FAC 61G1-16.003, |
| | 61G1.004(2)(5)(6) & FS 481.219, |
| | 481.2055. |
| | |
| | 2. ALL PLUMBING, MECHANICAL, FIRE, & |
| | ELECTRICAL SHEETS: ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME, ADDRESS AND |
| | LICENSE NUMBER ON EACH SHEET. IF |
| | PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE |
| | NUMBER, AS WELL AS, THE NAME, ADDRESS, |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS ON EACH |
| | SHEET. NOTE THAT THE BUSINESS NAME ON |
| | THE TITLE BLOCK IS DIFFERENT FROM THE |
| | BUSINESS REGISTERED WITH THE DBPR |
| | WEBSITE. (KLG/PAIGE INC.). PLEASE |
| | CORRECT TITLE BLOCKS THE REFLECT |
| | INFORMATION IN DBPR WEBSITE. (SEE |
| | ATTACHED SHEETS). |
| | |
| | 3. ALL PME & FIRE SHEETS. NEW SEAL |
| | REQUIRED FOR ENGINEER OF RECORD. |
| | "LICENSE" SHALL APPEAR ON ALL SEALS AS |
| | OF 01-01-06 AS THAT IS THE END OF A 2 |
| | YEAR GRACE PERIOD FROM THE FLORIDA BOARD |
| | OF PROFESSIONAL ENGINEERS. (SEE ATTACHED |
| | SHEET). |
| | |
| | 4. SHT A7.0 ELEVATION 1 A FORWARD |
| | APPROACH CLEAR FLOOR SPACE IS REQUIRED |
| | FOR THE BREAK ROOM SINK EXTENDING A |
| | MAXIMUM OF 19" UNDERNEATH THE SINK. |
| | CABINET DOORS ARE NOT APPROVED IN THE |
| | CLEAR FLOOR SPACE. SECTION 11-4.24.5. |
| | SHOW ON THE FLOOR PLAN. |
| | |
| | 5. SHT P1.0 WATER SUPPLY TO THE |
| | HUMIDIFIER SHALL HAVE BACKFLOW |
| | PROTECTION. SECTION 608.3. AN RPZV |
| | BACKFLOW WILL BE REQUIRED, AND BE |
| | INSTALLED A MAXIMUM 4' ABOVE THE FLOOR |
| | FOR SERVICING AND CERTIFICATION. PLEASE |
| | INDICATE ON PLANS. SECTION 608.13.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6713 |
| | E-MAIL [email protected] |
| | |