| 2006-04-26 00:00:00 | ************* UNSAT ********** |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS REFLECT |
| | THE FOLLOWING CODES. |
| | NFPA-101 2003, NFPA-70 2002, NFPA-72 |
| | 2002. PLEASE KNOW, THIS IS FOR |
| | ELECTRICAL AND ARCHITECTURAL SHEETS. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS FOR THE ARCHITECT, |
| | ARCHITECTURAL FIRM. |
| | PLEASE SEE MISSING THE PRINTED NAME, |
| | PRINTED LINCENSE # FOR SIAD ARCHITECT. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION #. |
| | PLEASE SEE ABOVE ALL REQUIRED UNDER THE |
| | FLORIDA ADMINISTIVE CODE 61G1-16.004 AND |
| | FLORIDA STATUES, 481.219 |
| | ** PLEASE KNOW THIS INFORMATION IS |
| | REQUIRED ON ALL SHEETS AND FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OF THE OTHER REVIEWERS. |
| | |
| | 3) NOTE: PLEASE SEE COPIES ATTACHED TO |
| | ELECTRICLA COMMENTS WITH RESPECT TO |
| | TITLE BLOCK(S) ON PLANS FOR ENGINEERING |
| | FIRM. |
| | PLEASE SEE CERTIFICATE OF AUTHORIZATION |
| | NUMBER AS INDICATED ON PLANS DO NOT |
| | CORRELATE WITH FIRM AS LISTED ON STATE'S |
| | WEBSITE. PLEASE SEE THE NUMBER AS SHOWN |
| | FOR A DIFFERENT COMPANY. |
| | PLEASE ALSO SEE ATTACHED COPY OF THE |
| | COMPANY AS LISTED ON STATE'S SITE WHICH |
| | INDICATES TWO OTHER KLG'S. "KLG INC", |
| | KLG, LLC, AND THE PREVIOUS MENTIONED |
| | "KLG/PAIGE INC. |
| | PLEASE UPDATE ALL LICENSE INFORMATION, |
| | PLEASE UPDATE ALL TITLE BLOCKS AS |
| | REQUIRED. |
| | ** PLEASE KNOW, THIS IS REQUIRED OF ALL |
| | TRADES AND FOR ALL MEP SHEETS CONTAINING |
| | THESE SAID TITLE BLOCKS. |
| | |
| | 4 )NOTE: PLEASE SEE PLANS MUST BE |
| | RE-SEALED AS THE SEAL AS SHOWN IS NO |
| | LONGER ACCEPTABLE AS PUBLIC RECORD FOR |
| | THE FLORIDA BOARD OF PROFESSINAL |
| | ENGINEER'S. PLEASE SEE FAC 61G15-23.001 |
| | WHICH IN FEB 04 CHANGED TO NOW REQUIRE |
| | ALL SEALS TO CONTAIN THE WORDING OF |
| | "LICENSE" AND COULD NO LONGER USE |
| | "CERTIFICATE". PLEASE KNOW, AN EXTENSION |
| | WAS GRANTED TO THE DATE OF 12/31/05 TO |
| | GIVE ALL ENGINEERS 2 YRS TO OBTAIN NEW |
| | SEALS. WE CAN NO LONGER ACCEPT OLD |
| | SEALS. |
| | ** PLEASE SEE THIS IS REQUIRED OF ALL |
| | SAID PLANS WITH SEAL FROM MR.DANNY |
| | LUNSTROM PE RESPECTIVELY. |
| | |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1, .2 AND .3. |
| | PLEASE SEE THE SYSTEM FOR ENERGY |
| | CONSERVATION SHALL BE BASED FOR ENTIRE |
| | AREA AND THE "OC" AS SHOWN MUST BE |
| | CAPABLE OF OVER-RIDING THE BASE SYSTEM. |
| | PLEASE PROVIDE INFORMATION ON TYOE OF OC |
| | BEING INSTALLED. |
| | PLEASE SEE SOME AREAS DO NOT INDICATE |
| | ALL CIRCUITING AS SHOWN AS PART OF THIS |
| | SYSTEM. |
| | PLEASE PROVIDE THE SCHEDULE FOR THESE |
| | FOR ALL AREAS. |
| | IT WAS NOTED THAT THE TIMED SPRING WOUND |
| | TIMER IS BEING INSTALLED IN SOME AREAS. |
| | PLEASE KNOW, COMMON AREA SHALL PROVIDE |
| | SOME SORT OF NOTICE FOR "LTS OUT" AND/OR |
| | EGRESS LTS PROVIDED. |
| | PLEASE PROVIDE DETAIL FOR THE |
| | OVER-RIDING OF THE TIME CLOCK SYSTEM AS |
| | NOTED ON PLANS. |
| | PLEASE SEE ABOVE REFERENCED CODES AS A |
| | OVERIDE DEVICE OF ONE OR MORE DEPENDING |
| | ON EGRESSED AREAS SHALL BE IN A READILY |
| | ACCESSIBLE LOCATION/ENTRANCE TO SPACE. |
| | |
| | 6) NOTE: PLEASE PROVIDE COMPLETE LOAD |
| | CALCUALTIONS ON PANELS INCLUDING NEW |
| | LOADS TO EXISTING. |
| | 215.5,,220.11,220.3,220.13 ETC. |
| | PLEASE BE SURE TO INDICATE ALL THE |
| | CONTINUOUS LOADS AT 125%. 215.3,230.42 |
| | |
| | 7) NOTE: PLEASE SEE PLAN NOTES MENTIONS, |
| | INSTALLATION FOR ROOMS CONTAINING |
| | COMPUTER EQUIPMENT TO MEET 645. |
| | PLEASE SEE "LAN RM", PLEASE PROVIDE |
| | DETAILED INFORMATION ON THIS ROOM AS IT |
| | SEEMS TO IMPLEMENT THE CRITERIA FOR AN |
| | "IT" ROOM. NFPA-75 |
| | PLEASE PROVIDE DETAILS FOR ANY AREA |
| | BEING CONSIDERED AS AN "IT" FOR |
| | DISCONNECTING MEANS, FIRE RATINGS FOR |
| | RM, A/C SHUT DOWN ETC. |
| | |
| | ** WHEN RESUBMITTING PLANS, PLEASE |
| | SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS |
| | FOR REFERENCE ONLY.. |
| | |
| | PLEASE BE AWARE OF ANY POSSIBEL COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | EELCTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITE IN CONTACTING THIS |
| | OFFICE. |
| | |