Plan Review Notes For Permit 06031168
Permit Number 06031168
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEALS AND TITLE BLOCKS ARE TO BE IN
 COMPLIANCE WITH FAC61G15-23.002,
 FAC61G1-16.003,004.THE SEAL HAS BEEN
 SIGNED BUT NOT DATED, AND CERTIFICATE OF
 AUTHORIZATION INFORMATION IS NOT ON THE
 PLAN.COMPLY WITH ALL REQUIREMENTS OF
 THE REFERENCED CODES, ALL DESIGN
 PROFESSIONALS.
  
 3.)PROVIDE DETAILS FOR THE ACCESSIBLE
 RESTROOMS.SEE FBC11-4.1.6(2)(2)(A).
 INCLUDE DIMENSIONS FOR THE TURNING
 RADIUS, CLEAR FLOORS SPACE FOR FIXTURES,
 FIXTURE DIMENSIONS, GRAB BARS.
  
 4.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FBC11-4.13.6, FIGURE 11-25, FOR
 THE BATHROOM DOORS AND CONFERENCE ROOM
 DOOR 526.
  
 5.)THE BREAK ROOM SINK IS TO BE
 ACCESSIBLE FBC11-4.24.THE SINK AS
 SHOWN LACKS THE KNEE CLEARANCE REQUIRED
 FBC-4.24.3.
  
 5.)THE PLAN SHOWS CORRIDORS WITH NO
 FIRE RATING.SEE FBC1002, DEFINITIONS.
  
 6.)INTERIOR FINISHED TO COMPLY WITH
 FBC TABLE 803.5.
  
 7.)THE LAN ROOM IS TO COMPLY WITH
 NFPA75.ALSO SEE FBC712 AS MECHANICAL
 SHEETS WILL REQUIRE REVISIONS.
  
 8.)THIS IS A LEVEL TWO ALTERATION, FBC
 EB304.
  
 9.)SHOW COMPLIANCE WITH FBC EB603.2,
 603.4.1.
  