| 2006-08-24 00:00:00 | ******REVISION DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW FOR THE SUBMITTED |
| | REVISION: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (NOTE: PLEASE INCLUDE |
| | ABOVE GROUND PIPE MEASUREMENTS AS WELL |
| | AS THE UNDERGROUND PIPE MEASUREMENTS ON |
| | THE REVISION.) |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | (NOTE: PLEASE INCLUDE ABOVE GROUND PIPE |
| | MATERIAL AS WELL AS UNDERGROUND PIPE |
| | MATERIAL ON THE REVISION.) |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING (ISOMETRIC) SHALL CLEARLY |
| | PRINT AND SIGN NAME, AND ALSO DATE |
| | DRAWING. PLEASE DO THIS PRIOR TO |
| | RESUBMITTING. |
| | |
| | 5. PER FBC-2004, CHAPTER 1, SECTION |
| | 106.1 SUBMITTAL DOCUMENTS. IF THE DESIGN |
| | PROFESSIONAL IS AN ARCHITECT LEGALLY |
| | REGISTERED UNDER THE LAWS OF THIS STATE |
| | REGULATING THE PRACTICE OF ARCHITECTURE |
| | AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART 1, FLORIDA STATUTES, THEN |
| | HE OR SHE SHALL AFFIX HIS OR HER SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA, AS |
| | REQUIRED BY FLORIDA STATUTES. |
| | |
| | END OF COMMENTS: |
| | |