| Plan Review Notes For Permit 06031114 |
| Permit Number |
06031114 |
|
| Review Stop |
G |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-04-06 16:16:34 | REVISION DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION REQUIRED FOR GAS | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PLEASE NOTE THAT ON SHEET M1.1 THERE IS AN APPROVED | | | GAS RISER THAT IS SIGNED AND SEALED BE DANIEL E. | | | THOMPSON FLA. REG. NO. 33289 OF THE "THOMPSON & | | | YOUNGROSS ENGINEERING CONSULTANTS, LLC" AND ANY | | | REVISIONS TO THAT GAS RISER NEEDS TO BE SIGNED AND | | | SEALED BY SAID DESIGN PROFESSIONAL PER CHAPTER 471, | | | FLORIDA STATUTES. PLEASE NOTE THAT A GAS PERMIT IS | | | REQUIRED FOR THIS WORK AND ONE HAS NOT BEEN ISSUED AS | | | OF THIS DATE 4/6/07. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|