| | FBC 2004 FUEL GAS CODE, PLAN REVIEW |
| | |
| | |
| | NEW COMMENTSUNSAT |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT. |
| | |
| | 1) SHT M1.1 GAS SYSTEM NOTES: |
| | REMOVE NOTES THAT DO NOT PERTAIN TO THE |
| | GENERATOR INSTALLATION. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED,FOR EACH PIPE SIZE BEING |
| | USED. |
| | |
| | 4. TYPE OF GAS, (LP OR NATURAL) |
| | |
| | 5.BTU LOAD OF GENERATOR UNDER FULL LOAD. |
| | REFER TO THE FBC-2004 FUEL GAS CODE |
| | SECS. 401.8 THRU 402.6.1 AND TABLES |
| | 402.4(1) THRU 402.4(33). |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE SYSTEM PER FBC-2004 FUEL |
| | GAS CODE APPENDIX A - USE OF CAPACITY |
| | TABLES A.3.1(4). |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 7 WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND, |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 8 SEE OTHER PLAN REVIEW COMMENTS, THAT |
| | MAY EFFECT PLUMBING PLAN REVIEW. |
| | |
| | |