Plan Review Notes
Plan Review Notes For Permit 06031114
Permit Number 06031114
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-06 00:00:00********** UNSAT2ND REVIEW ***********
  
 ** PLEASE SEE BELOW FOR NOTES FROM
 PREVIOUS REVIEW AN NEW NOTES WHICH NEED
 TO BE ADDRESSED.
  
 *** IMPORTANT **
 BEFORE RSUBMITTING PLANS!!
 MUST SUBMIT TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE SEE SOME SETS
 CONTAIN OLD SHEETS WHICH ARE STILL
 RELEVANT HOWEVER THESE ARE NOT IN NEW
 SETS. PLEASE SEE SOME ITEMS THERE IS
 ONLY ONE COPYOF AND IT IS REQUIRED TO
 SUBMIT TWO OF ALL ITEMS. PLEASE PLACE
 ALL ITEMS INTO TWO SETS IN A NEAT AND
 ORDERLY FASHION. THIS WILL HELP IN THE
 REVIEW PROCESS AND TO HELP EXPEDITE THE
 REVIEW PROCESS FOR PERMIT ISSUANCE..
 THIS OFFICE DOES NOT HAVE THE TIME TO DO
 THIS.
  
 1)NOTE: NO, PLEASE SEE THE SPECS WERE
 SUBMITTED, HOWEVER COULD NOT LCOATE ANY
 LISTINGS FROM ANY NRTL. THE CODE BELOW
 WHICH WAS REFERENCED IN PREVIOUS REVIEW
 WAS INCORRECT.SHOULD HAVE BEEN 110.3,
 90.8
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO SUBMIT ALL
 SPECS FOR ALL UPS SYSTEMS SHOWING A A
 LISTING FROM A NRTL.
 215.5
  
 2) NOTE:NO, PLEASE SEE GEN AND ATSARE
 OK, HOWEVER NOW UPON REVIEWING SPEC ON
 GEN, COULD NOT LOCATE THE WP HOUSING
 ASSOCITED WITH SAID GEN.
 FBC 106.1.2, 90.8
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GENERATOR AND ATS.
 UNABLE TO VERIFY SOME ITEMS FOR CODE
 COMPLIANCE.
  
 3) NOTE:OK, HOWEVER PLEASE SEE PLANS NOW
 REFLECT THE LATEST EDITION. PLEASE KNOW
 THE LATEST EDITON WOULD BE THE 2005 NEC,
 AND AS OF YET THE STATE OF FLORIDA HAS
 NOT ADOPTED SAID CODE. PLEASE LIST THE
 2002 NFPA-70 AND 2002 NFPA-110
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS REFERENCE THE
 2001 FBC.
 PLEASE KNOW AS OF OCT 1ST, 2005 THE NEW
 FBC 2004 IS IN EFFECT.
 PLEASE ALSO REFERENCE NFPA-110
 STANDARDS.
  
 4) NOTE: OK, NEW MAIN ADDED
  
 ** NEW NOTES **
  
 5) NOTE: AS STATED IN THE BEGINING OF
 THIS REVIEW PLEASE SUBMIT TWO COMPLETE
 SETS. PLEASE SEE ONE SET IS MISSING
 SHEET E2.1. PLEASE SEE SHEETS ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER
 OF RECORD.
 PLEASE ALSO SEE OTHER SHEET FOR A/C
 INFORMATION ARE SIGNED, DATED AND
 SEALED, HOWEVER NO TITLE BLOCKS ARE ON
 PLANS AS REQUIRED. FAC 61G15-23.002
 FS 471.025
  
 6) NOTE: PLEASE SEE DISTANCE FOR SET
 BACKS OF GEN COULD NOT LOCATED ON COPY
 OF THE SURVEYS, SITE PLANS OR LANDSCAPE
 PLANS SUBMITTED.
 PLEASE ALSO SEE ANY SITE LANDSCAPE PLANS
 DONE BY THE LANDSCAPE ARCHITECT AND
 FIRM, SHALL BE SIGNED, DATED AND SEALED,
 PER FS 481.321
 THIS IS REQUIRED EVEN IF COMMENT IS NOT
 MADE BY ZONING.
  
  
  
  
 ** PLEASE SEE POSSIBLE ZONING AND
 BUILDING COMMENTS, AS A SURVEY/SITE PLAN
 SHOWING ALL SETBACKS FOR LOCATION OF GEN
 WAS NOT SUBMITTED, AND ALSO A SLAB
 DETAIL AND ELEVATION COULD NOT BE
 LOCATED IN PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]