| Date |
Text |
| 2006-08-06 00:00:00 | ********** UNSAT2ND REVIEW *********** |
| | |
| | ** PLEASE SEE BELOW FOR NOTES FROM |
| | PREVIOUS REVIEW AN NEW NOTES WHICH NEED |
| | TO BE ADDRESSED. |
| | |
| | *** IMPORTANT ** |
| | BEFORE RSUBMITTING PLANS!! |
| | MUST SUBMIT TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. PLEASE SEE SOME SETS |
| | CONTAIN OLD SHEETS WHICH ARE STILL |
| | RELEVANT HOWEVER THESE ARE NOT IN NEW |
| | SETS. PLEASE SEE SOME ITEMS THERE IS |
| | ONLY ONE COPYOF AND IT IS REQUIRED TO |
| | SUBMIT TWO OF ALL ITEMS. PLEASE PLACE |
| | ALL ITEMS INTO TWO SETS IN A NEAT AND |
| | ORDERLY FASHION. THIS WILL HELP IN THE |
| | REVIEW PROCESS AND TO HELP EXPEDITE THE |
| | REVIEW PROCESS FOR PERMIT ISSUANCE.. |
| | THIS OFFICE DOES NOT HAVE THE TIME TO DO |
| | THIS. |
| | |
| | 1)NOTE: NO, PLEASE SEE THE SPECS WERE |
| | SUBMITTED, HOWEVER COULD NOT LCOATE ANY |
| | LISTINGS FROM ANY NRTL. THE CODE BELOW |
| | WHICH WAS REFERENCED IN PREVIOUS REVIEW |
| | WAS INCORRECT.SHOULD HAVE BEEN 110.3, |
| | 90.8 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO SUBMIT ALL |
| | SPECS FOR ALL UPS SYSTEMS SHOWING A A |
| | LISTING FROM A NRTL. |
| | 215.5 |
| | |
| | 2) NOTE:NO, PLEASE SEE GEN AND ATSARE |
| | OK, HOWEVER NOW UPON REVIEWING SPEC ON |
| | GEN, COULD NOT LOCATE THE WP HOUSING |
| | ASSOCITED WITH SAID GEN. |
| | FBC 106.1.2, 90.8 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT ALL MANUFACTURES |
| | CUT/SPEC SHEETS FOR GENERATOR AND ATS. |
| | UNABLE TO VERIFY SOME ITEMS FOR CODE |
| | COMPLIANCE. |
| | |
| | 3) NOTE:OK, HOWEVER PLEASE SEE PLANS NOW |
| | REFLECT THE LATEST EDITION. PLEASE KNOW |
| | THE LATEST EDITON WOULD BE THE 2005 NEC, |
| | AND AS OF YET THE STATE OF FLORIDA HAS |
| | NOT ADOPTED SAID CODE. PLEASE LIST THE |
| | 2002 NFPA-70 AND 2002 NFPA-110 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS REFERENCE THE |
| | 2001 FBC. |
| | PLEASE KNOW AS OF OCT 1ST, 2005 THE NEW |
| | FBC 2004 IS IN EFFECT. |
| | PLEASE ALSO REFERENCE NFPA-110 |
| | STANDARDS. |
| | |
| | 4) NOTE: OK, NEW MAIN ADDED |
| | |
| | ** NEW NOTES ** |
| | |
| | 5) NOTE: AS STATED IN THE BEGINING OF |
| | THIS REVIEW PLEASE SUBMIT TWO COMPLETE |
| | SETS. PLEASE SEE ONE SET IS MISSING |
| | SHEET E2.1. PLEASE SEE SHEETS ARE NOT |
| | SIGNED, DATED OR SEALED BY THE ENGINEER |
| | OF RECORD. |
| | PLEASE ALSO SEE OTHER SHEET FOR A/C |
| | INFORMATION ARE SIGNED, DATED AND |
| | SEALED, HOWEVER NO TITLE BLOCKS ARE ON |
| | PLANS AS REQUIRED. FAC 61G15-23.002 |
| | FS 471.025 |
| | |
| | 6) NOTE: PLEASE SEE DISTANCE FOR SET |
| | BACKS OF GEN COULD NOT LOCATED ON COPY |
| | OF THE SURVEYS, SITE PLANS OR LANDSCAPE |
| | PLANS SUBMITTED. |
| | PLEASE ALSO SEE ANY SITE LANDSCAPE PLANS |
| | DONE BY THE LANDSCAPE ARCHITECT AND |
| | FIRM, SHALL BE SIGNED, DATED AND SEALED, |
| | PER FS 481.321 |
| | THIS IS REQUIRED EVEN IF COMMENT IS NOT |
| | MADE BY ZONING. |
| | |
| | |
| | |
| | |
| | ** PLEASE SEE POSSIBLE ZONING AND |
| | BUILDING COMMENTS, AS A SURVEY/SITE PLAN |
| | SHOWING ALL SETBACKS FOR LOCATION OF GEN |
| | WAS NOT SUBMITTED, AND ALSO A SLAB |
| | DETAIL AND ELEVATION COULD NOT BE |
| | LOCATED IN PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |