2006-08-08 00:00:00PERMIT: 06031114
 ADD: 580 VILLAGE BLVD
 CONT: TEKTRON ELECTRICAL SYSTEMS
 TEL: (561)844-3156
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)2ND REQUEST,GENERATOR SLAB & ANCHOR
 REQUIREMENT, PLEASE PROVIDE SIZE OF
 GENERATOR(WXL), PLUS PROVIDE PLANS WITH
 THE INFORMATIONDEPICTING HOLD DOWN
 BRACKETS, TYPE OFFASTENER, AND THE
 MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
  
 THE PLANS INDICATE THE LENGTH OF
 THE SLAB MISSING THE WIDTH OF THE
 PROPOSED SLAB.
  
  
 2) 2ND REQUEST, 110.2* W. P. B.
 ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED. THIS DESIGN IS
 UNDER THE 2004 FBC, WHICH USES ASCE 7-02
 NOT 7-98. CORRECT. THE M).1 SHEET HAS A
 NOTE THAT THE DESIGN COMPLY WITH HIGH
 VELOCITY HURRICANE ZONE(FBC 1820.5).
 THIS IS A REQUIREMENET FOR DADE AND
 BROWARD COUNTIES UNENFORCEABLE IN PALM
 BEACH COUNTY.
 B) PROVIDE OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3. SOME
 OCCUPANCIES REQUIRE EMERGENCY GENERATORS
 WITH MINIMUM STANDARDS.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. AGAIN
 PROVIDE THE MINIMUM BUILDING TYPE, SOME
 BUILDING TYPES REQUIRE GENERATORS WITH
 MINIMUM STANDARDS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026