2006-04-26 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE BE SURE TO SUBMIT ALL
 SPECS FOR ALL UPS SYSTEMS SHOWING A A
 LISTING FROM A NRTL.
 215.5
  
 2) NOTE:PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GENERATOR AND ATS.
 UNABLE TO VERIFY SOME ITEMS FOR CODE
 COMPLIANCE.
  
 3) NOTE: PLEASE SEE PLANS REFERENCE THE
 2001 FBC.
 PLEASE KNOW AS OF OCT 1ST, 2005 THE NEW
 FBC 2004 IS IN EFFECT.
 PLEASE ALSO REFERENCE NFPA-110
 STANDARDS.
  
 4) NOTE: PLEASE MEANS OF DISCONNECT FOR
 POWER COMING FROM GENERATOR SHALL BE
 GROUPED WITH EXISTING MAIN(S).
 230.72,230.76,230.79, 225.31-225.39.
 UNABLE TO VERIFY AT THIS TIME AS
 EXISTING MAIN FOR BUILDING IS NOT SHOWN.
  
  
 ** PLEASE SEE POSSIBLE ZONING ABD
 BUILDING COMMENTS, AS A SURVEY/SITE PLAN
 SHOWING ALL SETBACKS FOR LOCATION OF GEN
 WAS NOT SUBMITTED, AND ALSO A SLAB
 DETAIL AND ELEVATION COULD NOT BE
 LOCATED IN PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 ** PLEASE BE AWARE OF COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE PLANS
 SUBMITTED.