| Plan Review Notes For Permit 06031107 |
| Permit Number |
06031107 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-05 00:00:00 | *** USNAT 2ND REVIEW *** | | | | | | 1) NOTE: PLEASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW WHICH REQUESTED TO | | | PLEASE PROVIDE NEW OR SHWOING NEW | | | EMERGENCY EGRESS AND NORMAL EGRESS | | | LIGHTING AS REQUIRED IN NFPA-101 | | | 7.8.1.3, 7.9.2.2 | | | PLEASE PROVIDE MIN FT CANDLES AS | | | SPECIFIED. | | | PLEASE SEE PLANS SHALL ALSO BE SPECIFIC | | | TO THE CODES IN REFERENCE. | | | SEE 101, IS FROM THE 2003 CURRENTLY AS | | | ADOPTED BY THE STATE OF FLORIDA. | | | | | | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS AND | | | REPEAT COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|