| Plan Review Notes For Permit 06031107 |
| Permit Number |
06031107 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-17 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE MISSING INFORMATION | | | ON TITLE BLOCKS PER FAC 61G15-23.002, FS | | | 471.023. | | | PLEASE ALSO SEE PLANS APPEAR TO BE | | | SIGNED WITH "INITIALS", IF INDEED THIS | | | IS THE "LEGAL" SIGNATURE FOR SAID | | | ENGINEER, PLEASE PROVIDE A SIGNED, DATED | | | AND SEALED LETTER NOTING LEGAL | | | SIGNATURE. PLEASE KNOW, THE LETTER MUST | | | BE PROPERLY NOTORIZED PER FS117.05. | | | THIS LTR WILL BE PLACED IN OUR SIGNATURE | | | FILE FOR FUTURE REFERENCES. | | | | | | 2)NOTE: PLEASE INDICATE NEW OR EXISTING | | | LIGHTING FOR MEANS OF EGRESS TO THE | | | PUBLIC RIGHT OF WAY. | | | PLEASE SEE 2003 NFPA-101, 7.8.1.3 WHICH | | | REQUIRES A MIN OF 10 FT CANDLES UNDER | | | NORMAL CONDITIONS AND 1FT CANDLE UNDER | | | EM CONDITIONS. | | | PLEASE SEE 7.9.2.2 FOR SOME SORT OF | | | BATTERY BACK UP FIXTURE REQUIRED FOR A | | | MIN OF 90MIN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|