Plan Review Notes
Plan Review Notes For Permit 06031107
Permit Number 06031107
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-17 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS PER FAC 61G15-23.002, FS
 471.023.
 PLEASE ALSO SEE PLANS APPEAR TO BE
 SIGNED WITH "INITIALS", IF INDEED THIS
 IS THE "LEGAL" SIGNATURE FOR SAID
 ENGINEER, PLEASE PROVIDE A SIGNED, DATED
 AND SEALED LETTER NOTING LEGAL
 SIGNATURE. PLEASE KNOW, THE LETTER MUST
 BE PROPERLY NOTORIZED PER FS117.05.
 THIS LTR WILL BE PLACED IN OUR SIGNATURE
 FILE FOR FUTURE REFERENCES.
  
 2)NOTE: PLEASE INDICATE NEW OR EXISTING
 LIGHTING FOR MEANS OF EGRESS TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE SEE 2003 NFPA-101, 7.8.1.3 WHICH
 REQUIRES A MIN OF 10 FT CANDLES UNDER
 NORMAL CONDITIONS AND 1FT CANDLE UNDER
 EM CONDITIONS.
 PLEASE SEE 7.9.2.2 FOR SOME SORT OF
 BATTERY BACK UP FIXTURE REQUIRED FOR A
 MIN OF 90MIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]