| 2006-03-27 00:00:00 | ****DENIED**** | | | REFERENCE FBC-2004 FUEL GAS AND CITY OF | | | WEST PALM BEACH, AMENDMENTS TO FBC-2004 | | | CHAPTER 1 ADMINISTRATION: | | | | | | 1. NOTE: PER SEC. 106 CONSTRUCTION | | | DOCUMENTS, CITY OF WEST PALM BEACH, | | | AMENDMENTS TO FBC-2004, CHAPTER 1, | | | ADMINISTRATION. IF IT IS YOUR INTENT TO | | | USE THE BRENNER ARCHITECTURE GROUP INC, | | | TITLE BLOCK, THE DRAWING NEEDS TO BE | | | SIGNED AND SEALED BY SAID DESIGN | | | PROFESSIONAL. IF THIS IS NOT YOUR IN- | | | TENT THEN REMOVE SAID TITLE BLOCK AND | | | GAS SYSTEM DESIGNER SHALL SIGN DRAWINGS. | | | 2. ISOMETRIC DRAWING DOES NOT REFLECT | | | THE FLOOR PLAN. | | | 3. CSST SIZED WRONG WITH WRONG TABLE, | | | NEEDS TO BE SIZED BY FBC-2004 TABLE | | | 402.4(14). PLEASE CORRECT AND SEE | | | ENCLOSED LETTERS AND SIZING TABLES FOR | | | YOUR REFERENCE FOR RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|