Plan Review Notes
Plan Review Notes For Permit 06031104
Permit Number 06031104
Review Stop G
Sequence Number 1
Notes
Date Text
2006-03-27 00:00:00****DENIED****
 REFERENCE FBC-2004 FUEL GAS AND CITY OF
 WEST PALM BEACH, AMENDMENTS TO FBC-2004
 CHAPTER 1 ADMINISTRATION:
  
 1. NOTE: PER SEC. 106 CONSTRUCTION
 DOCUMENTS, CITY OF WEST PALM BEACH,
 AMENDMENTS TO FBC-2004, CHAPTER 1,
 ADMINISTRATION. IF IT IS YOUR INTENT TO
 USE THE BRENNER ARCHITECTURE GROUP INC,
 TITLE BLOCK, THE DRAWING NEEDS TO BE
 SIGNED AND SEALED BY SAID DESIGN
 PROFESSIONAL. IF THIS IS NOT YOUR IN-
 TENT THEN REMOVE SAID TITLE BLOCK AND
 GAS SYSTEM DESIGNER SHALL SIGN DRAWINGS.
 2. ISOMETRIC DRAWING DOES NOT REFLECT
 THE FLOOR PLAN.
 3. CSST SIZED WRONG WITH WRONG TABLE,
 NEEDS TO BE SIZED BY FBC-2004 TABLE
 402.4(14). PLEASE CORRECT AND SEE
 ENCLOSED LETTERS AND SIZING TABLES FOR
 YOUR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  