| Plan Review Notes For Permit 06031101 |
| Permit Number |
06031101 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-03 00:00:00 | | | | | | | DENIED | | | | | | 1) THOSE PRODUCTS WHICH ARE REGULATED BY | | | DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | *****PLEASE SUBMIT UPDATED COVER LETTER | | | LISTING ALL REVIEWED AND APPROVED | | | PRODUCT APPROVALS***** | | | | | | 2) SUBMIT ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND | | | DATED BY PREPARER AND OWNER/AGENT PRIOR | | | TO SUBMITTAL | | | | | | *****ENERGY CALC'S DO NOT MATCH DRAWINGS | | | PLEASE SEE THAT DRAWING SPECIFIES R-30 | | | INSULATION IN THE CEILING AND THE ENERGY | | | CALC'S SHOW R-19***** | | | | | | 3) PRODUCT APPROVAL FOR CLOPAY SECTIONAL | | | DOOR HAS A MAXIMUM WIDTH OF 9'-0" WHILE | | | THE DRAWING SPECIFIES A 7X16 GARAGE DOOR | | | | | | 4) PER 713.13(2) F.S. | | | IF THE IMPROVEMENT DESCRIBED IN THE NOC | | | HAS NOT COMMENCED WITHIN 90 DAYS OF | | | RECORDING THE NOTICE IS VOID | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | |
|