| Plan Review Notes For Permit 06031101 |
| Permit Number |
06031101 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-10 00:00:00 | LOAD CALCULATION ONLY SHOWS NEW LOADS NO | | | EXISTING LOADS SHOWN. | | | | | | NEED PANEL SCHEDULE. | | | | | | GFCI IN KITCHEN AND OUTLET SPACING NOT | | | TO CODE IN KITCHEN. | | | | | | ARC FAULTS IN BEDROOMS. | | | | | | PLANS NOT SIGNED. | | | | | | SMOKE DETECTORS NOT SHOWN. | | | | | | CALL PHILLIP PETTY805-6742 |
|