Plan Review Notes
Plan Review Notes For Permit 06031101
Permit Number 06031101
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-24 00:00:00 
  
 DENIED
  
 1) INDICATE 2004 FBC AND CORRECT WIND
 LOAD TABLES 1609.6 A-E
  
 2) FOOTING TYPE NOTES ON S/1 SEND TO
 WRONG DETAILS PLEASE VERIFY
  
 3) NO PRECAST LINTELS SHOWN ON S/1 BUT
 PRODUCT APPROVALS WERE SUBMITTED. BEAM
 HEIGHT 8'-1", WINDOW AND DOOR HEIGHT
 6'-8" LEAVES ONLY 5". IS TIE BEAM POURED
 DOWN OVER DOORS AND WINDOWS, PLEASE
 VERIFY, IF SO REMOVE LINTEL PRODUCT
 APPROVALS
  
 4) BEAM SPANS ON S/2 REQUIRE ENGINEERED
 INTERPOLATION TO CLARIFY THAT SPANS OF
 TRIPLE 2X12 WILL CARRY THE LOADS FOR
 SPANS OVER 12'-2" AS SHOWN IN CHAPTER 23
 TABLE 2308.9.5 FBC
  
 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 6) SUBMIT ENERGY CALC'S FOR NEW ADDITION
 PER 106.3.5.4 (10) FBC*
  
 7) ADDITION WILL REQUIRE MECHANICAL
 DRAWINGS TO BE SUBMITTED
  
 8) SURVEY IS REQUIRED TO SHOW ALL
 CHANGES TO THE FOOTPRINT OF THE BUILDING
 UPDATE SURVEY TO INCLUDE THE LANAI WHICH
 IS COVERED BY THE MAIN ROOF STRUCTURE
  
 9) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC* (APPLICATION HAS BEEN
 ADJUSTED)
  
 10) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC (APPLICATION
 HAS BEEN ADJUSTED)
  
 11) PROVIDE WINDOW SIZES ON REPLACEMENT
 WINDOWS
  
 12) PRODUCT APPROVALS WERE NOT SUBMITTED
 FOR ROOF COVERING, GARAGE DOOR, FIXED
 WINDOW, FRECH DOORS, SINGLE DOOR INTO
 GARAGE OR STORM SHUTTERS
  
 13) MARK THE MULL SIZE THAT WILL BE USED
 (PAGE 4 OF NOA) AS THERE ARE DIFFERENT
 PRESSURES FOR EACH TYPE
  
 14) THE THERMA-TRU STATE COVER SHEET
 DOES NOT COVER "BENCHMARK SERIES" UNDER
 FL# 5262. THE MIAMI-DADE NOA MAY BE
 SUBMITTED FOR LOCAL PRODUCT APPROVAL IF
 NO STATE COVER IS AVAILABLE, BUT YOU
 MUST PROVIDE LOCATION OF THIS PRODUCT.
 THE NOA IS FOR DOUBLE DOORS IS THIS FOR
 FRONT ENTRY OF LANAI ?
  
 15) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 16) STRUCTURAL REQUIREMENTS SHALL
 INCLUDE A WALL SECTION FROM FOUNDATION
 THROUGH ROOF, INCLUDING ASSEMBLY AND
 MATERIALS, CONNECTOR TABLES, WIND
 REQUIREMENTS, AND STRUCTURAL
 CALCULATIONS PER 106.3.5.4 (6) FBC*
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  