| Plan Review Notes For Permit 06031084 |
| Permit Number |
06031084 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-11 00:00:00 | DENIED | | | | | | 1) THE SYSTEM YOU SELECTED FROM THE | | | TAMKO NOA THAT WAS SUBMITTED IS FOR USE | | | AS A TILE UNDERLAYMENT. SELECT A SYSTEM | | | THAT CAN BE USED FOR A FLAT ROOF AND | | | CIRCLE THE DESIGN PRESSURE FOR THE | | | FASTENING METHOD THAT WILL BE USED. | | | | | | 2) THE HIGHEST MAXIMUM DESIGN PRESSURE | | | FOR THE SYSTEMS LISTED IN THE TAMKO NOA | | | IS -60 PSF. THE REQUIRED DESIGN PRESSURE | | | FOR THE CORNERS IS -89 PSF PER FBC TABLE | | | 1609.6B. THEREFORE, ENHANCED FASTENING | | | PER RAS 117 WILL BE REQUIRED. THIS IS | | | ALLOWED FOR SOME OF THE ASSEMBLIES BY | | | LIMITATION NUMBER 7 ON THE LAST PAGE OF | | | THE NOA. HOWEVER, THISLIMITATION ALSO | | | REQUIRES THAT THESE CALCULATIONS ARE | | | SIGNED AND SEALED BY AN ENGINEER, | | | ARCHITECT OR REGISTERED ROOFING | | | CONSULTANT. | | | | | | 3) THE NOA THAT IS LISTED WITH THE STATE | | | FOR THE GAF ROYAL SOVERIGN SHINGLE IS | | | NOA 04-0820.01. PLEASE SUBMIT TWO COPIES | | | OF THIS NOA. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|