| Plan Review Notes For Permit 06031084 |
| Permit Number |
06031084 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-23 00:00:00 | DENIED | | | | | | 1) ENHANCED FASTENING IS REQUIRED TO | | | INCREASE DESIGN PRESSURE FOR TAMKO | | | MODIFIED SYSTEM. NOA LIMITATION NUMBER 7 | | | REQUIRES THESE CALCULATIONS TO BE DONE | | | BY ENGINEER, ARCHITECT OR REGISTERED | | | ROOF CONSULTANT. SUBMIT SIGNED AND | | | SEALED CALCULATIONS. | | | | | | 2) SUBMIT THE UPDATED COVERSHEET FROM | | | THE STATE FL #183-R1 AND THE | | | CORRESPONDING NOA 04-0820.01. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|