2006-03-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATION INDICATES A 250
 AMP MAIN BREAKER, THE RISER DIAGRAM
 SHOWS 2/0 CONDUCTORS FOR THE SERVICE
 FROM THE METER TO THE MAIN
 DISCONNECT.THE MINIMUM CONDUCTOR SIZE IS
 4/0 COPPER PER 310.15(B(6). ALSO THE
 CONDUCTORS IN THE RISER AND THE CONDUIT
 SIZE AND TYPE ARE NOT IDENTIFIED.
  
 2} THE OCP FOR CIRCUITS 19'21'26'28 IN
 PANEL "A", AND 18 THROUGH 22 IN PANEL
 "B" IS TOO LARGE FOR THE CONDUCTORS, 20
 AMP FOR #14 WIRE. SEE 310.16.
  
 NOTE: THE TOTAL LOAD FOR THE SERVICE IS
 207 AMPS ON A 250 AMP SERVICE. THERE IS
 A PROPOSED POOL, THIS REVIEW WOULD
 RECOMMEND A LARGER SERVICEFOR FUTURE
 INCREASED LOADS. PLEASE SEE ARTICLE
 90.1(A) AND THE FPN.
  
 3} A LIGHT IS REQUIRED FOR EXTERIOR
 ILLUMINATION AT THE EXTERIOR SERVICE
 DOOR PER 210.70(A)(2)(B).
  
 4} A SMOKE DETECTOR IS REQUIRED IN
 BEDROOM #5 PER R313 FBC.
  
 5} ELECTRICAL NOTE #3 INDICATES GFI
 PROTECTION FOR RECEPTACLES WITHIN 6'
 OF THE KITCHEN SINK. PLEASE SEE
 210.8(A)(6), ALL COUNTERTOP RECEPTACLES,
 REGERDLESS OF LOCATION. ALSO NOTE #7
 REFERS TO THE 1996 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  