| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE LOAD CALCULATION INDICATES A 250 |
| | AMP MAIN BREAKER, THE RISER DIAGRAM |
| | SHOWS 2/0 CONDUCTORS FOR THE SERVICE |
| | FROM THE METER TO THE MAIN |
| | DISCONNECT.THE MINIMUM CONDUCTOR SIZE IS |
| | 4/0 COPPER PER 310.15(B(6). ALSO THE |
| | CONDUCTORS IN THE RISER AND THE CONDUIT |
| | SIZE AND TYPE ARE NOT IDENTIFIED. |
| | |
| | 2} THE OCP FOR CIRCUITS 19'21'26'28 IN |
| | PANEL "A", AND 18 THROUGH 22 IN PANEL |
| | "B" IS TOO LARGE FOR THE CONDUCTORS, 20 |
| | AMP FOR #14 WIRE. SEE 310.16. |
| | |
| | NOTE: THE TOTAL LOAD FOR THE SERVICE IS |
| | 207 AMPS ON A 250 AMP SERVICE. THERE IS |
| | A PROPOSED POOL, THIS REVIEW WOULD |
| | RECOMMEND A LARGER SERVICEFOR FUTURE |
| | INCREASED LOADS. PLEASE SEE ARTICLE |
| | 90.1(A) AND THE FPN. |
| | |
| | 3} A LIGHT IS REQUIRED FOR EXTERIOR |
| | ILLUMINATION AT THE EXTERIOR SERVICE |
| | DOOR PER 210.70(A)(2)(B). |
| | |
| | 4} A SMOKE DETECTOR IS REQUIRED IN |
| | BEDROOM #5 PER R313 FBC. |
| | |
| | 5} ELECTRICAL NOTE #3 INDICATES GFI |
| | PROTECTION FOR RECEPTACLES WITHIN 6' |
| | OF THE KITCHEN SINK. PLEASE SEE |
| | 210.8(A)(6), ALL COUNTERTOP RECEPTACLES, |
| | REGERDLESS OF LOCATION. ALSO NOTE #7 |
| | REFERS TO THE 1996 NEC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |