Plan Review Notes
Plan Review Notes For Permit 06031064
Permit Number 06031064
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-03 00:00:00CONT: LENNAR HOMES
 TEL: (561)790-0202
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. PLEASE CREATE (2) SETS OF PLANS
 FROM ALL THE LOOSE SHEETS. THANK YOU FOR
 YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) 3RD REQUEST, THE SALES TRAILER IS
 LOCATED IN A FLOOD ZONE "AO". PLEASE
 PROVIDE THE ELEVATION THAT THE BOTTOM OF
 THE SALES TRAILER WILL BE SET AT.
 PROVIDE FLOOD ZONE ELEVATION CERTIFICATE
 FOR NEW CONSTRUCTION WITH BASE FLOOD
 ELEVATION. REQUIRED INFO:
 "AO FLOOD ZONE"
 PANEL# 120192 0150 A
 DATE 2/1/79
 IF LOMAR FOR SITE PLEASE PROVIDE LOMAR.
  
 THE ELEVATION CERTIFICATE PROVIDED IS
 NOT FOR 8763 BAYWINDS DR BUT FOR 9770
 BOWLINE DR.
  
 NOTE IS A DOCUMENT REQUIRED BEFORE A
 C. O. WILL BE ISSUED. THE BUILDING
 SHOULD NOT BE SET MAKING IT THAT THE
 SURVEYOR CAN NOT PROVIDE A CERTIFICATE
 AT THIS TIME.
  
 6) 2ND REQUEST, PLANS DO NOT PROVIDE
 ENOUGH INFORMATION AS TO ACCESSIBLE
 ROUTE, RAMPAGE STRUCTURAL PLANS FOR RAMP
 ACCESS TO SALES TRAILER. 11-4.1.3(1) AT
 LEAST ONE ACCESSIBLE ROUTTE COMPLYING
 WITH 11-4.3 SHALL CONNECT ACCESSIBLE
 BUILDING OR FACILITY ENETRANCES WITH ALL
 ACCESSIBLE SPACES AND ELEMENTS WITHIN
 THE BUILDING OR FACILITY.
 THE LANDSCAPE PLAN SHOWS AN ARIAL
 VIEW, BUT NO INFORMATION, NO DETAILS,
 AS TO HOW TO BUILD THE STAIRS RAMPS OR
 HANDRAILS.
 6A) ACCESSIBLE ROUTE AND RAMPAGE:
 NEITHER THE LANDSCAPE PLAN NOR THE A-1
 SHEET INDICATE WHAAT MATERIALS THE
 PARKKING LOT, ACCESSIBLE AISLE OR
 WALKWAYS WILL CONSIST OF.DEFINITIONS
 11-3:ACCESSIBLE ROUTE . A CONTINUOUS
 UNOBSTRUCTED PATH CONNECTING ALL
 ACCESSIBLE ELEMENTS AND SPACES OF A
 BUILDING OR FACILITY. INTERIOR
 ACCESSIBLE ROUTES MAY INCLUDE CORRIDORS,
 FLOORS, RAMPS, ELEVATORS, LIFTS, AND
 CLEAR FLOOR SPACE AT FIXTURES. EXTERIOR
 ACCESSIBLE ROUTES MAY INCLUDE PARKING
 ACCESS AISLES, CURB RAMPS, CROSSWALKS AT
 VEHICULAR WAYS, WALKS, RAMPS AND LIFTS.
 6B) RAMP:A-1 INDICATES THE BOTTOM
 LANDING TO BE 18". 11-4.8.4(2)ALL
 LANDINGS ON RAMPS SHALL BE NOT LESS THAN
 60 INCHES (1524 MM) CLEAR, AND THE
 BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72 INCHES (1829 MM) OF STRAIGHT AND
 LEVEL CLEARANCE.
 6C) THE PLANS INDICATE THE DECK TO BE
 24'X8'. THE FRONT OF THE DECK INDICATES
 (2) 2X12 WITH A TOTAL OF 4 POST CARRYING
 THE WEIGHT OF THE DECK WHEREAS THE BACK
 OF THE DECK ONLY INDICATE (1) 2X12 AND
 (2) END POST, ISN'T THE LOADS TO BE
 CARRIED THE SAME. PLANS DO NOT SHOW
 FLOOR JOIST CONNECTIONS IF NAILS OR IF
 JOIST HANGERS ARE REQUIRED.
 6D) PLANS DO NOT INDICATE IF WOOD IS TO
 BE PRESSURE TREATED. 2304.11.4 WOOD IN
 CONTACT WITH THE GROUND OR FRESH WATER.
 WOOD IN CONTACT WITH THE GROUND (EXPOSED
 EARTH) THAT SUPPORTS PERMANENT
 STRUCTURES SHALL BE OF NATURALLY DURABLE
 (SPECIES FOR BOTH DECAY AND TERMITE
 RESISTANCE) OR PRESERVATIVE-TREATED WOOD
 USING WATER-BORNE PRESERVATIVES AND
 SHALL BE TREATED IN ACCORDANCE WITH AWPA
 C2, C9 OR OTHER APPLICABLE AWPA STANDARD
 FOR SOIL OR FRESH WATER CONTACT, WHERE
 USED IN THE LOCATIONS SPECIFIED IN
 SECTIONS 2304.11.4.1 AND 2304.11.4.2 .
 2304.11.2 WOOD USED ABOVE GROUND.
 WOOD INSTALLED ABOVE GROUND IN THE
 LOCATIONS SPECIFIED IN SECTIONS
 2304.11.2.1 THROUGH 2304.11.2.6 SHALL BE
 NATURALLY DURABLE WOOD OR
 PRESERVATIVE-TREATED WOOD THAT USES
 WATER-BORNE PRESERVATIVES, AND SHALL BE
 TREATED IN ACCORDANCE WITH AWPA C2 OR C9
 OR APPLICABLE AWPA STANDARDS FOR
 ABOVE-GROUND USE.
 6D)THE STAIRS ARE DIMENSIONED AS 7 1/2"
 RISERS.1009.3STAIR RISER HEIGHTS SHALL
 BE 7 INCHES (178 MM) MAXIMUM AND 4
 INCHES (102 MM) MINIMUM. STAIR TREAD
 DEPTHS SHALL BE 11 INCHES (279 MM)
 MINIMUM.
 6E) PLANS INDICATE A 31" RISE FROM GRADE
 TO THE TOP OF DECK. GUARDRAILS 1012.1
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED
 WALKING SURFACES, MEZZANINES, INDUSTRIAL
 EQUIPMENT PLATFORMS, STAIRWAYS, RAMPS
 AND LANDINGS WHICH ARE LOCATED MORE THAN
 30 INCHES (762 MM) ABOVE THE FLOOR OR
 GRADE BELOW.
 6F)1012.3 OPENING LIMITATIONS.
 OPEN GUARDS SHALL HAVE BALUSTERS OR
 ORNAMENTAL PATTERNS SUCH THAT A
 4-INCH-DIAMETER (102 MM) SPHERE CANNOT
 PASS THROUGH ANY OPENING UP TO A HEIGHT
 OF 34 INCHES (864 MM). FROM A HEIGHT OF
 34 INCHES (864 MM) TO 42 INCHES (1067
 MM) ABOVE THE ADJACENT WALKING SURFACES,
 A SPHERE 8 INCHES (203 MM) IN DIAMETER
 SHALL NOT PASS.
 6G) HANDRAILS:11-4.9.4(3)THE CLEAR SPACE
 BETWEEN HANDRAILS AND WALL SHALL BE 1?
 INCHES (38 MM).
  
 7)COMPLIED.
  
 8) COMPLIED.
  
 9) SAME AS 6B REQUIRING A 72" BOTTOM
 LANDING ON RAMP.
  
 10) COMPLIED.
  
 11) HANDRAILS, SEE COMMENT 6G) CLEAR
 DISTANCE BETWEEN THE HANDRAIL AND
 PICKETS.
  
 12) NEW COMMENT: SHEET A-1 INDICATES
 PLANS DESIGNED TO THE 2001 FBC.
  
 BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026