| Plan Review Notes For Permit 06031064 |
| Permit Number |
06031064 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ***DENIED*** | | | | | | PLEASE NOTE THAT COMMENTS FROM LAST FIRE | | | REVIEW DO NOT APPEAR TO BE ADDRESSED. | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, AND NFPA 1, 2003 EDITIONS. | | | | | | 2) INTERIOR FINISH CLASSIFICATION FOR | | | TEMPORARY STRUCTURES TO BE CLASS A ONLY. | | | | | | | | | 3) HOW LONG WILL THIS STRUCTURE BE UP? | | | THIS CODE ALLOWS FOR 180 DAYS. | | | | | | 4) PLEASE SHOW LOCATION OF EMERGENCY | | | LIGHTING FACILITIES ON PLANS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|