| Plan Review Notes For Permit 06031055 |
| Permit Number |
06031055 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-11 00:00:00 | | | | | | | DENIED | | | | | | 1) CBC LICENCE DOES NOT ALLOW STRUCTURAL | | | OR SPECIALTY CONTRACTORS WORK OUTSIDE OF | | | THE LIMITATIONS OF A CBC LICENCE. | | | (CAN NOT WORK ON MULTIPLE DWELLING | | | RESIDENTIAL BUILDINGS IN EXCESS OF 3 | | | STORIES OR 36 FT) | | | | | | 2) SGD PRODUCT APPROVALS SHALL BE MARKED | | | WITH TYPE OF DOOR, TYPE OF REINFORCING, | | | TYPE OF ATTACHMENT, DOOR PANEL SIZES, | | | ETC. | | | | | | 3) SHUTTER PRODUCT APPROVAL SHALL BE | | | MARKED WITH MOUNTING METHOD, FASTENER | | | TYPE, ETC. | | | | | | 4) LIST ALL DOOR SIZES AND DOOR PANEL | | | SIZES | | | | | | 5) LIST ALL SHUTTER SPANS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|