| Plan Review Notes For Permit 06031031 |
| Permit Number |
06031031 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-10 00:00:00 | | | | | | | DENIED | | | | | | 1) ROLL-UP SHUTTER NOA IS MARKED FOR | | | ALLOWABLE SPAN ON PAGE 4 OF 14. THE | | | SHUTTER SPAN IS 11'- 4" AND AT THE | | | DESIGN PRESSURE REQUIRED WILL NEED A | | | STORM BAR AS IN TABLE 2 | | | | | | 2) ACCORDIAN NOA IS OK | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|