| Plan Review Notes For Permit 06031026 |
| Permit Number |
06031026 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-30 00:00:00 | ******DENIED 2ND TIME****** | | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW FOR A PERMIT: | | | | | | 1) FBC-2004 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | | SHEETS REQUIRED,PLEASE SUBMIT) | | | 2) FBC-2004 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF.(MANUFACTURE SHEETS REQUIRED, PLEASE | | | SUBMIT) | | | 3) PLEASE INDICATE ON THE POOL HEATER | | | MANUFACTURE SHEETS REQUESTED THE MODEL | | | BEING USED, AND THAT THEY CORRELATE WITH | | | THE POOL SPECIFICATIONS. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|