| Plan Review Notes For Permit 06031026 |
| Permit Number |
06031026 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-10 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING | | | INFORMATION REQUIRED FOR PLAN REVIEW: | | | | | | 1. THE TWENTY FOUR INCH (24") SHEER | | | DECENT WITH AN INCH AND A HALF (1-1/2") | | | SUPPLY LINE AND VALVE NEED TO BE | | | INDICATED ON EQUIPMENT LAYOUT. | | | 1. PRINT NEEDS TO CORRELATE WITH POOL | | | HEATER SUBMITTAL. PRINT INDCATES A | | | 305,000 BTU GAS HEATER AND THE SUBMITTAL | | | INDICATES A 399,000 BTU GAS HEATER. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|