| 2006-04-12 00:00:00 | |
| | |
| | |
| | DENIED |
| | |
| | 1) SUBMIT PLAN OF WALLS TO BE REMOVED OR |
| | RELOCATED. |
| | |
| | 2) SUBMIT LIST WITH DESCRIPTION OF WORK |
| | TO BE DONE |
| | |
| | 3) NO TRADES ARE LISTED ON APPLICATION |
| | THEREFORE ANY WORK FOR ELECTRICAL, |
| | PLUMBING , ETC. TO BE UNDER SEPARATE |
| | PERMITS |
| | |
| | 4) WITH REMOVAL OF FLOORING, PLACEMENT |
| | OF SOUND TRANSMISSION REDUCING MEMBRANE |
| | SHALL BE REQUIRED PER SECTION 1207 FBC |
| | |
| | 5) WIND LOAD CRITERIA FOR COMPONANTS AND |
| | CLADDING SUCH AS DOORS AND WINDOWS SHALL |
| | BE DETERMINED BY AN ENGINEER FOR |
| | BUILDINGS OVER 60 FEET PERSECTION 1609 |
| | FBC. THIS INFORMATION IS REQUIRED BEFORE |
| | PRODUCT APPROVALS CAN BE REVIEWED FOR |
| | COMPLIANCE |
| | NOTE: GIVE DIMENSIONS OF SLIDING GLASS |
| | DOORS TO BE REPLACED |
| | |
| | 6)THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | |
| | 7) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | |