| 2006-08-24 00:00:00 | DENIED; |
| | 1.ADA DETAIL FOR PHASE 11 ON PAGE A-2 |
| | ONLY SHOWS A DETAIL OF THE LAVATORY. |
| | DETAIL OF THE WHOLE BATHROOM IS REQUIRED |
| | SHOW THE TOILET, SHOWER, AND LAVATORY IN |
| | DETAIL. REQUIREMENTS FOR COMPLIANCE CAN |
| | BE FOUND, FBC-2004 CHAPTER 11; TOILET, |
| | 11-4.16.1 THRU 11-4.16.6; LAVATORY |
| | SECTIONS 11-4.19.1 THRU 11-4.19.6; |
| | SHOWER SECTIONS 11-4.21.1 THRU |
| | 11-4.21.8. |
| | 2.HOT WATER REQUIRED TO SERVICE SINK. |
| | (SHOW ON PLAN) SHOW LOCATION OF WATER |
| | HEATER, OR WATER HEATERS, SIZE AND FUEL |
| | SOURCE. |
| | 3.SANITARY RISER DIAGRAM; |
| | A)TRENCH DRAIN AND FLOOR DRAIN SHALL |
| | NOT BE DOUBLE TRAPPED. SEC 1002.1 |
| | B)WHAT IS THE 4" VERTICAL DRAIN AND |
| | BACK WATER VALVE FOR? NEED MORE |
| | INFORMATION) |
| | C)WHY IS A FLOOR DRAIN NEEDED IN THE |
| | FUTURE PAINT BOOTH? (SECOND REQUEST) |
| | 4.SAND INTERCEPTER; (SECOND REQUEST) |
| | PLANS MUST BE VIEWED AND APPROVED BY THE |
| | UTILITY DEPTMENT FOR SIZE AND LOCATION. |
| | THE CONTACT PERSON IS; |
| | LYNN MASSON |
| | PHONE # 822-2271 |
| | FAX# 822-2279 |
| | E-MAIL [email protected] |
| | 5.PLUMBING FIXTURE REQUIREMENT TABLE FOR |
| | PHASE 11 IS NOT CORRECT. WORK WILL BE |
| | DONE IN THIS PART OF THE BUILDING. |
| | PLEASE CHANGE CLASIFICATION TO BUSINESS, |
| | OR CHANGE BOTH PHASES TO BUSINESS. |
| | PLUMBING PLAN REVIEW BY; |