| 2006-07-15 00:00:00 | DENIED; |
| | 1.PROVIDE INFORMATION ON SPRAY BOTH. WHY |
| | WOULD A FLOOR DRAIN BE REQUIRED? |
| | 2.PLEASE SHOW A DETAIL OF NEW HANDICAP |
| | BATHROOM. BATHROOM MUST MEET FBC-2004 |
| | CHAPTER 11; |
| | SHOWER SECTIONS 11-4.21.1 THRU |
| | 11-4.21.8. |
| | LAVATORY SECTIONS 11-19.1 |
| | THRU11-4.19.6 |
| | SHOW TURNING RADIUS IN BATHROOM ON |
| | DRAWING. |
| | 3.HANDICAP CODE SECTION 11-4.1.3(11) |
| | BOTH BATHROOMS MUST BE ACCESSIBLE. |
| | 4.MINIMUM PLUMBING FIXTURES, FBC-2004 |
| | PLUMBING TABLE 403.1(8) REQUIRES A MOP |
| | SINK AND A DRINKING FOUNTAIN. DRINKING |
| | FOUNTAIN MUST MEET HANDICAP CODE |
| | SECTIONS 11-4.15.1 THRU 11-4.15.5, AND |
| | SECTION 11-4.1.3(11). |
| | 5.PLANS MUST BE REVIEW BY THE UTILITY |
| | DEPARTMENT FOR SIZE AND LOCATION OF SAND |
| | AND OIL INTERCEPTOR. |
| | THE CONTACT PERSON IS; |
| | LYNN MASSON |
| | PHONE (561) 822-2271 |
| | FAX(561) 822-2279 |
| | [email protected] |
| | 6.DETAIL OF SAND AND OIL INTERCEPTOR IS |
| | REQUIRED. HOW IS PIPING TO BE INSTALLED |
| | (INSIDE THE TANK) TYPE OF MATERIAL TANK |
| | IS MADE FROM. SHOW COMPLIANCE WITH |
| | SECTIONS 1003.4 THRU 1003.4.2. ALSO |
| | 1003.9 VENT IS REQUIRED. |
| | 7.EMERGENCY EYE WASH AND SHOWER STATION |
| | SHOULD BE IN A CENTRAL LOCATION NEAR THE |
| | PAINT STORAGE AND PREP AREA, ALSO A DOOR |
| | TO THE SPAY BOOTH SHOULD BE ON THE SIDE |
| | OF THE EMERGENCY EQUIPMENT. |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |