| 2006-07-12 00:00:00 | 1. ALL VEHICLES ON DISPLAY SHALL HAVE | | | THE BATTERIES DISCONNECTED AND CONTAIN | | | VERY LITTLE FUEL. THIS ITEM WAS VERIFIED | | | WITH OGS&P ON 7/12/06 BY PHONE. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE PROPOSED SPRAY BOOTH AND MIXING | | | ROOM. BOTH WILL BE REQUIRED TO BE | | | PROTECTED WITH AN AUTOMATIC FIRE | | | SUPPRESSION SYSTEM UNDER SEPARATE | | | PERMIT. THE SPRAY BOOTH SHALL COMPLY | | | WITH NFPA 33. | | | | | | 3. COULD NOT LOCATE ANY CUT SHEETS ON | | | CARBON MONOXIDE DETECTORS THAT ARE | | | PLANNED FOR USE IN THE LITERATURE. | | | PLEASE PROVIDE PRODUCT LITERATURE AND | | | HOW WILL THESE DEVICES BE TESTED. | | | CALIBRATION GAS AND TEST EQUIPMENT WILL | | | MOST LIKELY BE NEEDED IF THE SET POINTS | | | ON THESE DETECTORS DO NOT COME FACTORY | | | SET. PLEASE PROVIDE MORE DETAILS AS | | | REQUIRED. | | | | | | 4. ALL WORK SUBJECT TO FIELD INSPECTION | | | AND APPROVAL. PLEASE HAVE THE PROJECT | | | ARCHITECT CONTACT THIS OFFICE AT | | | 804-4709. THANK YOU. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|