| Date |
Text |
| 2006-07-02 00:00:00 | IN ELEC FOR REVIEW |
| | ******** UNSAT 2ND REVIEW ******** |
| | |
| | |
| | 1) NOTE: PLEASE SEE ELECTRICAL PLANS |
| | WHICH DID NOT INDICATE VEHICLE LIFTS AND |
| | SPRAY BOOTH ON PREVIOUS PLANS, NOW |
| | INDICATE THIS AS SOME SORT OF SERVICE |
| | REPAIR/BODY SHOP. |
| | PLEASE SEE NEC 511 AND 516. ALL AREAS AN |
| | CLASS LOCATION SHALL BE INDICATED AND |
| | LAYED OUT PER NEC 500, 500.5, 501, CLASS |
| | 1 DIV 1, CLASS 1 DIV 2? |
| | NFPA-88B, 1997 |
| | PLEASE SEE THIS SHOWN WITH A "WAREHOUSE" |
| | OCCUPANCY WHICH DOES NOT SEEM TO |
| | CORRELATE WITH NEW REVISED PLANS AND |
| | PROPOSED WORK. |
| | |
| | 2) NOTE: PLEASE SEE PLANS NOW INDICATE |
| | AN OPEING TO ADJACENT SPACE WHICH IS |
| | ANOTHER TENANT, ADDRESS AND OCCUPANCY |
| | FOR "VEHICLE STORAGE". |
| | THIS ADDITONAL METERED SERVICE MAY NOT |
| | BE GRANTED AT THIS TIME. |
| | "SEPARATION" IS NOT ACHEIVED BY THE |
| | OVERHEAD DOOR, AS THIS CAN BE OPENED AT |
| | ANY TIME AND LEFT IN THE OPEN POSITION. |
| | PLEASE SEE TWO DIFFERENT PROJECTS ARE |
| | COMING IN FOR PERMIT, WHICH SEEM TO BE |
| | INFACT THE SAME BUSINES, SPACE ETC. |
| | ** PLEASE KNOW, THESE ARE BEING STATED |
| | AS TWO SEPARATE "BUILDINGS"?? PLEASE SEE |
| | DEFINITIONS OF "BUILDING" AND SEPARATION |
| | REQUIRED BYE A "FIREWALL". PLEASE SEE |
| | "FIREWALL" AND CONSTRUCT ACCORDINGLY. |
| | PLEASE KNOW, AT THAT TIME THE SECOND |
| | SERVICE AND METER WILL BE GRANTED. |
| | 230.2 |
| | |
| | |
| | 3) NOTE: PLEASE SEE THAT PLANS REFLECT |
| | ALL CURRENT CODES IN EFFECT. |
| | NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| | 2002 AND FBC 2004. PLEASE SEE PLANS |
| | REFERENCE THE 2001 FBC. |
| | |
| | 4) NOTE:PLEASE SEE FBC CHAPTER 13 |
| | WHICH APPLIES TO THIS SPACE. |
| | PLEASE PROVIDE LIGHTING DENSITES FOR |
| | AREAS. |
| | PLEASE PROVIDE OVER RIDES AS REQUIRED |
| | AND INDICATE THE MAX AMOUNT OF TIME FOR |
| | DEVICES CHOSEN. (TIMERS 4HRS MAX) , OCC |
| | SENSORS 30MINS MAX). |
| | PLEASE SEE ENERGY CALCULATIONS SHALL BE |
| | SIGNED, DATED AND SEALED BY ALL DESIGN |
| | PROFESSIONALS RESPONSIBLE. |
| | PLEASE SEE THESE ONLY CONTAIN A |
| | SIGNATURE AT THIS TIME. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3 |
| | PLEASE SEE 13-415.1.AB.1, |
| | 13-415.2.ABC.1, AND TABLES 415.2.C1, |
| | 415.2.B.1 |
| | |
| | 5) NOTE: PLEASE KNOW, "IF" ADDITIONAL |
| | SERVICE IS GRANTED , PLEASE BOND BOTH |
| | SERVICES AT THE GROUNDING ELECTRODE |
| | SYSTEM.250.94,250.90 ETC |
| | |
| | 6) NOTE: ** IMPORTANT" AS REQUESTED BY |
| | THE BUIDLING REVIEWER ON PREVIOUS NOTES: |
| | ONCE ALL REVIEWS ARE COMPLETE, BEFORE |
| | RESUBMITTING PLANS, PLEASE COMPLETELY |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. ONE COPY |
| | OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP TO ALLEAVIATE ANY DELAYS |
| | INTHE PROCESS. |
| | |
| | ** PLEASE KNOW, ONE SET OF EACH OF THE |
| | PREVIOUS SUBMITTED ELECTRICAL PLANS |
| | ALONG WITH THE NEW REVISED ELECTRICAL |
| | PLANS ARE BEING RETAINED BY THIS OFFICE |
| | AS EACH SET CONTAINS COMPLETELY |
| | DIFFERENT INFORMATION FOR USE/OCCUPANCY |
| | ETC. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELETRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, OR COMMENTS |
| | PLEASE CALL. |
| | A CALLED WAS PLACED TO THE ELECTRICAL |
| | ENGINEER'S OFFICE AND A MESSAGE WAS LEFT |
| | AS OF THIS REVIEW TO GO OVER PLANS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |